26
3062878_201707
10. Operating level 2
wolf-heiztechnik.de
Contractor
Password: 1234
Alarm management
Service
Backup mode
Night ventilation
Limits
Contractor menus
DISPLAYSELECTIONEsc BACK
10.2 Heating contractor menu
Standard mask
Main menu
Heating contractor
Setting heating contractor parameters
The Wolf logo will be displayed. Pressing prompts entry of the heating contractor
password (1234), which can then be changed with .Byconrmingwith you
reach the heating contractor menu. There, by pressing you select from the
menu points displayed. After selecting the required menu point you enter the required
sub-menu by pressing
. Pressing
returns you to the standard display. If
no adjustment was made for more than 2 minutes, the standard display will return
automatically.
Overview:
→
Alarm management
→
Service
→
Backup mode
→
Night ventilation
→
Limits
→
Preheat program
→
Pump control
→
Air dampers
→
Cooling
→
Compensation
→
Temperature control
→
Extension time
→
Peak ventilation
→
Air quality
→
Pressure/owratectl
→
Humidity control
→ HRIce guard
→
Other…
Filter monitor
Frost protection
Airowmonitoring
Alarm memory
------------------------------
Alarm management menus
DISPLAYSELECTIONEsc BACK
10.2.1 Alarm management
Standard mask
Main menu Heating contractor
Alarm management
Adjusting parameters concerning alarm messages and functions as well as
displaying the alarm history.
Pressing enables selection between the overview of the illustrated menu points.
After selecting the required parameter you enter the required sub-menu by pressing
.
Overview:
→
Filter monitor
→
Frost protection
→
Airowmonitor
→
Alarm memory