Main menu Heating contractor Other...
User settings and interfaces can be adjusted and additional sensors can be
conguredlater.
Password
The password for the heating contractor level can be matched to individual
customer requirements.
BMK key lock
If this parameter is set to "Yes", the key lock is enabled after 2 minutes
without any intervention.
Pressing and holding down the
button (for approx. 3 seconds) cancels
the key lock temporarily.
To disable the key lock permanently, set this parameter to "NO".
BMK-F key lock
Individual keys can be locked to restrict the function range of the remote
control unit.
Optional entry of Wolf order number
The order number of the unit can optionally be entered. This allows
additional information to be called up if the unit is connected to the portal.
The order number can be found on the type plate of the relevant unit.
Post-conguration
Itispossibletoretrotaremotecontrol,touchpanel,airqualitysensor,
supply air pressure sensor, process air pressure sensor, room temperature
sensor, extract air temperature sensor, external OFF contact and a
hygrostat, if required.
Please note
Fundamental function extensions, such as cooling function or pressure
regulation,forexample,requirearecongurationofthecontrolunit.
Save / load parameter set
Customer-specicparametersettingscanbesaved
(e.g. the condition of the system when commissioned) and reloaded
when required.
It is also possible to restore the factory settings.
Please note
Itisnotpossibletoloadsettingsifthecontrolunithasbeenrecongured,
becausetheinternaldatamemoryisclearedduringreconguration.