10. Operating level 2
SP compensation
0.0 K
Summer:
START at:
END at:
DISPLAYSELECTIONEsc BACK
24.0 °C
36.0 °C
10.2.10 Compensation
(condition: outside and room
temperature sensor installed)
SW-01
Parameter Setting range Factory setting
Summer 0 - 4 K 0 K
Start at outside temperature 2 - 42 °C 24 °C
End at outside temperature 2 - 42 °C 36 °C
Winter 0 - 4 K 0 K
Start at outside temperature -15 - 15 °C 5 °C
End at outside temperature -15 - 15 °C -15 °C
Standard mask
Esc
Main menu
Heating contractor
Compensation
Summer compensation:
In cooling mode, the set room temperature is adjusted subject to outside
temperature. In other words, at high outside temperatures, the room temperature
is raised in accordance with these parameters. This prevents excessively high
temperature differentials between the room temperature and the outside temperature.
In addition, this reduces the energy expended on cooling.
Set room
temperature
Maximum
compensation
Outside temperature
End temperatureStart temperature
Selected
set value
Please note
In "Summer" or "Winter" = 0 this function is disabled
(no compensation).
Winter compensation
In heating mode, the set room temperature is adjusted subject to outside
temperature. This increases the set room temperature when outside temperatures
are very low.
Set room
temperature
Maximum
compensation
Outside temperature
End temperature Start temperature
Selected
set value