Main menu Heating contractor Peak
ventilation
The peak ventilation can be activated either in the standard settings or via the
BMK-F remote control. When peak ventilation is active, the fresh air proportion,
the fan stage, the fan speed, the pressure or the air volume are increased to a
programmed value. The "Runtime" parameter will only be valid if the activation took
place at the programming module. The time can be selected at the remote control, if
the activation was made at the BMK-F remote control.
10.2.13 Peak ventilation
SL-01
DISPLAYSELECTIONEsc BACK
Peak ventilation
Runtime 20 min
Parameter Setting range Factory setting
Runtime 5 - 300 min 20 min
Fresh air 0 - 100 % 100 %
Fan stage Stage 1 - 3 Stage 3
Fan speed 0 - 100 % 100 %
Pressure 0 - 1000 Pa 250 Pa
Flow rate 0 - 120,000 m³/h 1000 m³/h
Standard mask
Main menu Heating contractor Extension time
The extension of utilisation time can be activated either in the standard
settings or via the BMK-F remote control. When the extension of utilisation
time is activated, the system runs for at least the time set. The extension
time can be selected at the remote control, if the extension of utilisation time
is activated via the BMK-F remote control. If the extension of utilisation time
is activated whilst the system is shut down, it will start for the selected time.
The set values last active will become active again.
Setback mode makes the stop times in the time program overlap subject to
outside temperature. It can be enabled or disabled.
This function counteracts any formation of ice on the external units, since
moisture rising through the duct is permanently removed from the appliance.
This function will be active when it is enabled and when the outside
temperature lies below the set limit.
During this time, the fans will run at the set minimum speed and the fresh air
damper will be switched to minimum fresh air proportion.
Special operating modes that increase the speed or fresh air proportion (for
example air quality regulation etc.) remain disabled during setback mode.
Parameter Setting range Factory setting
Extension time 5 - 720 min 30 min
Enable setback mode
Yes/No No
Outside temp limit for setback mode -20 - 50 °C 0 °C