49
3062878_201707
Parameter Setting range Factory setting
New password 0 - 9999 1234
BMK key lock Yes/No No
BMS-Protocol No proto./LON-Works/
BACnet/pCO Manager/
Modbus/Ethernet/KNX
Subject to order
Transfer rate 1200/2400/4800/
9600/19200/38400
4800*
9600**/***
19200****
BMS-Address 0 - 200 1
Stop bit 1 - 2 1
Parity None / Even / Odd None
BMK-F key lock
ON / OFF key
Locked / Enabled Enabled
Manual / auto key Locked / Enabled Enabled
Speed key Locked / Enabled Enabled
Fresh air key Locked / Enabled Enabled
Extension time key Locked / Enabled Enabled
Peak ventilation key Locked / Enabled Enabled
Increase / decrease value keys Locked / Enabled Enabled
Remote control present Yes/No Subject to order
Touch panel present Yes/No Subject to order
Air quality sensor present Yes/No No
Vent. air pressure sensor present Yes/No No
Extract air pressure sensor
present
Yes/No No
Room temperature sensor
available
Yes/No Subject to order
Extract temperature sensor
available
Yes/No Subject to order
Remote ON/OFF switch available Yes/No Subject to order
Hygrostat available Yes/No Subject to order
Save customer settings Yes/No No
Load customer settings Yes/No No
Load factory settings Yes/No No
Reconguration,controlunit Yes/No No
* if LON interface is present
** if KNX interface is present
*** if a Modbus interface is present
**** if a BACnet or Ethernet interface is present
Parameter setting list for "Other"
10. Operating level 2