10. Operating level 2
Parameter Setting range Factory setting
Enable, preheat program Yes/No Yes
Preheat below outside temperature -20 - 15 °C 10 °C
Preheat time, heater bank 1 - 30 min 2 min
Min. fan speed when KGWO active 0 - 100 % 30 %
Min. fan stage when KGWO active 1 - 3 1
Min. damper position when KGWO
active
0 - 100 % 20 %
Minimum runtime, heat source demand 0 - 20 min 6 min
Minimum set boiler temperature 40.0 - 90.0 °C 50 °C
Maximum set boiler temperature 50.0 - 90.0 °C 80 °C
Minimum outside temperature -30.0 - 15.0 °C -15.0 °C
Maximum outside temperature 10.0 - 40.0 °C 15.0 °C
Heat source demand
As soon as a demand is issued to the heating circuit pump, a demand will
also be issued to the heat source. A minimum runtime can be set.
Weather-compensated set boiler temperature
If there is BUS communication between the Wolf heating control unit and
the Wolf air handling control unit, the set boiler water temperature can be
speciedbytheairhandlingcontrolunitaccordingtodemand.Thisallows
theowtemperaturetobematchedtotherequiredheatingoutputoftheair
handlingsystem,therebyavoidinganunnecessarilyhighowtemperature.
Flow temperature in °C
Outside temperature °C
Max. set boiler temp.
Min. set boiler temp.
Min. Max.