46
3062878_201707
10. Operating level 2
Parameter Setting range Factory setting
Prop. fresh air for
hygrostat function
0 - 100 % 100 %
Fan stage for
hygrostat function
1 - 3 3
Fan speed for
hygrostat function
0 - 100 % 80 %
Continuous hygrostat function
Start
0 - 100 % r.h. 60 % r.h.
End 0 - 100 % r.h. 80 % r.h.
Continuous hygrostat function
Max. speed
20 - 100 % 100 %
Continuous hygrostat function
Max. stage
Stage 1-3 Stage 3
Continuous hygrostat function
Max. fresh air rate
0 - 100 % 100 %
Automatic start for
hygrostat function
Yes/No No
Set humidity level (relative) 10 - 95 % r.h. 50 % r.h.
Set humidity level (absolute) 2 - 30 g/kg 8 g/kg
Max. r.h., vent. air 50 - 100 % r.h. 90 % r.h.
Minimumhumidiercontrol 0 - 100 % 35 %
Minimumhumidierruntime 0 - 99 min 0 min.* / 10 min.**
Humidierrun-ontime,drying 0 - 99 min 10 min.* / 2 min.**
Enable below outside
temperature
Yes/No No
Enable below outside
temperature
0 - 40 °C 15 °C
Delay, temperature priority
control
0 - 60 min 5 min.
Humidierstartdelay 0 - 99 min 5 min.* / 2 min.**
Reference temp. for set
humidity level
Actual temperature /
set temperature
Actual temperature
*withadiabatichumidier
**withisothermalhumidier
To determine the absolute humidity, use the h,x diagram.
As an example, the absolute humidity (9.4 g/kg) at a temperature of 24 °C and a
relative humidity of 50 % has been calculated.
Parameter setting list for
"Humidity control"