60 3064298_201507
Contractor
parameter
Meaning Setting range Factory setting Individual setting
System
WP001 Systemconguration 01, 02, 05, 11, 12, 14,
15, 33, 34, 51, 52
01
WP002 Function input 1 (E1)
none none
RT
DHW
RT/DHW
Zirkomat
TPW / Max Th
WP003 Functionoutput1(A1)*
none none
Timer20
Timer50
Timer100
Alarm
Zirkomat
Defrost
Add ht gn
Compressor ON
Heating HTG
WP010 Set spread / offset 0.0 ... 10.0 °C 5.0 °C
WP011 Heating hysteresis 0.5 ... 3.0 °C 2.0 °C
WP012 ZHPrun-on 0 min ... 30 min 1 min
WP013
Delay for heating by add. ht generator, heating
1 min ... 180 min 60 min
WP014 HCP run-on 0 min ... 30 min 5 min
WP015 HC pump rate, maximum 70 % ... 100 % 100 %
WP016 Enabling spread control Off, On On
WP017 Max. boiler temp. HTG TV-max 40.0 ... 70.0 °C 55 °C
WP018 Min. boiler temp. BWT-min 10.0 ... 40.0 °C 20 °C
Domestic hot water DHW
WP020 Cylinder hysteresis 1.0 ... 10.0 °C 2.0 °C
WP021 Enable max. cylinder heating time Off, On ON
WP022 Max. cylinder heating time 30 min ... 240 min 120 min
WP023
Delay for heating by add. ht generator, DHW
1 min ... 180 min 60 min
WP024 Minimum DHW temperature 10.0 °C ... 55.0 °C 45.0 °C
Smart grid
WP025 Smart grid Off, On Off
WP026 External raising, HTG 0.0 - 20.0 °C 0.0 °C
WP027 External raising, DHW 0.0 - 20.0 °C 0.0 °C
WP028 External activation Off, heat pump, heat
pump and electric
heating
Off
WP031 BUS address 1, 2, 3, 4, 5 1
Active cooling
WP053 Outside temp. enable cooling 15.0 … 40.0 °C 25.0 °C
WP054 Min.owtemp.forcooling 5.0 … 25.0 °C 20.0 °C
WP055 Offsetsetowtemp,cooling 5.0 … 20.0 °C 15.0 °C
WP058 Enable active cooling Off, On Off
31.3.1 Overview of contractor parameters for split heat pump: