62 3064298_201507
Contractor
parameter
Description
WP001 Forsettingapre-conguredsystemversionsubjecttoheatpumpdesignand
application(see"Overviewofsystemcongurations").
WP002 For optionally assigning one of the following functions to programmable input E1:
Code Function input E1
None No function
RT Heating block (room thermostat)
Contact open - blocked
Contact closed - heating mode enabled
DHW DHW block
Contact open - blocked
Contact closed - DHW mode enabled
RT/DHW Heating and DHW block
Contact open - blocked
Contact closed - heating mode and DHW mode enabled
Zirkomat Zirkomat (DHW circulation remote control)
WheninputE1isconguredastheDHWcirculationremote
control, output A1 is automatically set to "DHW circulation
pump" and is blocked for further settings. When input E1 is
closed, output A1 is activated for 5 minutes. When input E1 has
switched off and 30 minutes have elapsed, the remote control
function is re-enabled for the next operation.
TPW / Max Th Dew point monitor / max. thermostat
Contact open -
Cooling mode/heating mode/DHW mode blocked
Contact closed -
Cooling mode/heating mode/DHW mode enabled
31.3.2 Description of contractor parameters