633064298_201507
Contractor
parameter
Description
WP003 For optionally assigning one of the following functions to programmable input E1:
Code Function output A1
None No function
Timer20 DHW circulation pump activation 20 % (2 mins on, 8 mins off)
Timer50 DHW circulation pump activation 50 % (5 mins on, 5 mins off)
Timer100 DHW circulation pump activation 100 % (continuous operation)
Alarm Alarm output
Is set if a fault is present.
Zirkomat Zirkomat (DHW circulation remote control)
Output A1 is activated for 5 minutes when input E1 closes. If
outputA1Zirkomatiscongured,inputE1isautomaticallyset
to "DHW circulation remote control" and is blocked for further
settings. When input E1 has switched off and 30 minutes have
elapsed, the remote control function is re-enabled for the next
operation.
Defrost ODU in defrost mode
Is set if the heat pump is defrosting.
E.g.forusewiththeBMSconguration
Add ht gn Additional heat generator
Is set if demand is issued to additional heat generator.
(Onlypossiblewithcongurations33and34.)
Note:
Theelectricboosterheaterisdeactivatedforcongurations33
and 34 as long as compressor and additional heat generator
are operational.
Compressor ON Compressor active
Is set if the compressor is active.
WP010 WP016 = ON:
Forsettingthesetspreadbetweenowandreturntemperatures(heatingmode).
WP016 = OFF:
For setting the offset for the deactivation point in heating mode.
For this, the temperatures at the return sensor and the header sensor are monitored.
Heat pump OFF:
T_return / T_header > T_Boiler set – WP010 + WP011
Heat pump ON:
T_return / T_header < T_Boiler set – WP010 – WP011
WP011 For setting the hysteresis value to WP010.
WP012 Forsettingtherun-ontimeofthefeed/heatingcircuitpump(ZHP).
WP013 For setting the delay time for activation of the electric heating/additional heat
generator in heating mode.
WP014 For setting the run-on time of the heating circuit pump of the direct heating circuit
(HCP).
31. Contractor level