64 3064298_201507
Contractor
parameter
Description
WP015 WP016=On:
Forsettingthemaximumspeedofthefeed/heatingcircuitpump(ZHP).
WP016=Off:
Forsettingtheconstantspeedofthefeed/heatingcircuitpump(ZHP).
WP016 Enables spread control (controlling to set spread WP010) and PWM actuation
(WP015)ofthefeed/heatingcircuitpump(ZHP).
WP017 Forsettingthemax.owtemperaturelimit(T_boiler).
With screed drying function for setting the maximum temperature.
WP018 Forsettingthemin.owtemperaturelimit(T_boiler).
With screed drying function for setting the constant temperature.
WP020 For setting the hysteresis value for DHW heating or DHW cylinder heating.
WP021 Enables a maximum heating time for the DHW cylinder.
WP022 For setting the maximum heating time for the DHW cylinder.
WP023 For setting the delay time for activation of the electric heating / additional heat
generator for DHW heating.
WP024 For setting the minimum DHW temperature for ECO mode.
WP025 Enables the smart grid function.
WP026 Forraisingthesetowtemperature(T_Boilerset)forheatingmodesothattheheat
pumpisactivatedatadenedpoint.
WP027 For raising the set DHW temperature (T_DHW set) so that the heat pump is activated
atadenedpoint.
WP028 For selecting whether an activation command via smart grid switches on just the
compressor, or the compressor plus the electric heating.
WP031 If multiple heat sources are controlled in one heating system with a cascade module,
addresses must be allocated to the heat sources.
WP053 For setting the minimum outside temperature for active cooling mode.
WP054 Forsettingtheminimumowtemperature(T_boiler)oftheactivelycooledheating
circuits.
WP055 For setting the offset value or the differential between the outside temperature and
thesetowtemperature(T_Boilerset)oftheactivelycooledheatingcircuits.
(T_Boiler set = T_outside - Offset (WP055)).
WP058 Enable function for active cooling.
WP080 Dual mode point for deactivation of the compressor.
WP090 Enables the electric heating for heating mode.
WP091 Dual mode point for activation of electric heating for heating mode
WP092 For setting power-OFF for the electric heating.
WP093 Deactivation of the dual mode point (WP091) of the electric heating for the set period.
Serves the screed drying function, to ensure that the electric heating supports the
heat pump.
WP094 For setting the installed electric heating or setting the actual installed connected load
of the electric heating.
WP101 Dual mode point for activation of the additional heat generator.
WP121 Serves to limit the compressor start-ups per hour.
31. Contractor level