EasyManua.ls Logo

Worcester Greenstar 8000 Life GR8300iW 30 R

Worcester Greenstar 8000 Life GR8300iW 30 R
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings in the service menu
Greenstar 8000 Life – 6720883866 (2019/04)
50
Menu 6 (L.6) Function tests
Press the ( key and * key at the same time, until L.A is displayed.
Keep pressing the arrow key , until L.6 is displayed.
To confirm the selection: Press the OK key.
Select and set the service function.
The basic settings are depicted as highlighted in the following table.
Table 22 Menu 6: Function tests
Menu 0 (L.0) Manual mode
Press the ( key and * key at the same time, until L.A is displayed.
Keep pressing the arrow key , until L.0 is displayed.
To confirm the selection: Press the OK key.
Select and set the service function.
The basic settings are depicted as highlighted in the following table.
Table 23 Menu 0: Manual mode
7.3 Thermal disinfection
To prevent hot water from becoming contaminated by bacteria such as
legionella, we recommend thermal disinfection after long downtimes.
CAUTION:
Risk of scalding.
During thermal disinfection, discharging unmixed hot water can cause
serious scalding.
Only use the maximum adjustable hot water temperature for thermal
disinfection.
Inform occupants of the premises of the risk of scalding.
Perform thermal disinfection outside of the normal operating times.
Do not discharge DHW unmixed.
Proper thermal disinfection involves the DHW system including the
draw-off points.
Set the thermal disinfection in the hot water program of the heating
controller ( heating controller operating instructions).
Close DHW draw-off points.
Set any DHW circulation pump to continuous operation.
Wait until the maximum temperature is reached.
Open all DHW draw-off points, from the nearest to the one furthest
away, and draw off hot water until hot water at a minimum of 70 °C
has flown from all draw-off points for at least 3 minutes.
Restore the original settings.
Service function L.6 Settings/adjustment range Remark/restriction
6-t1 Ignition OFF
•ON
Testing the ignition by means of 8s on and 2s off
without gas supply.
To prevent damage to the ignition
transformer: Leave the function switched on
for a maximum of 2 minutes.
6-t2 Fan OFF
•ON
Permanent fan operation.Fan operation without
gas supply or ignition.
6-t3 Continuous pump running (heating
pump)
OFF
•ON
If ON is set, the pump runs at 100 %.
6-t4 DHW charge pump OFF
•ON
Depends on the hydraulic configuration 2-A3.
6-t5 3-way valve 0: Heating
1: DHW
2: Middle position
The function ensures that the system is fully
drained and that the motor can be easily
removed. The 3-way valve remains at the centre
position for approx. 15 minutes.
6-t7 HC1 pump OFF
ON
This service function is only available, if service
function 2-A3 is set to 2.
6-t8 DHW circulation pump OFF
•ON
Depends on the settings of 3-C2.
6-t9 Solar pump OFF
•ON
Permanent pump run.
This service function is only available, if a solar
module is installed.
6-tA Ionisation oscillator OFF
•ON
Check the ionisation measurement function at the
flame.
6-tb Burner OFF...100 % The burner test is ended, if the setting value is set
to OFF again, or if L.6 is exited.
Service function L.0 Settings/adjustment range Remark/restriction
0-A1 Manual mode OFF
•ON
Allows manual control of heating during loss of RF Key
signal. Set the desired heating flow temperature.
0-A2 Set temperature for manual mode 30 …70 °C This service function will only be available, if service
function 0-A1 is activated.

Table of Contents

Related product manuals