EasyManua.ls Logo

Worcester Greenstar 8000 Life GR8300iW 30 R

Worcester Greenstar 8000 Life GR8300iW 30 R
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Inspection and maintenance
53
Greenstar 8000 Life – 6720883866 (2019/04)
Fan pressure test reading.
The pressure reading will be in negative values.
Fig. 71 Fan pressure test values
Appliance fan pressure test values
Natural Gas and LPG appliances
Table 24 Natural Gas and LPG appliances
[] Cleaning required
[] No cleaning required
If the manometer reading is higher then the appliance output value
[P] mbar.
The heat exchanger/exhaust path/siphon does not require attention.
If the manometer reading shows the heat exchanger requires
cleaning, then carry out the following checks.
Check that the siphon is not restricted or blocked.
Check the exhaust paths for restrictions.
Clean the heat exchanger with a suitable cleaning tool, refer to
cleaning section.
Re-check the fan pressure readings.
If the boiler, after completing the above checks, fails the fan pressure
test then contact Worcester, Bosch Group for advice.
Replace test point cover after completing pressure check.
8.6 Check working gas inlet pressure
NOTICE:
Gas inlet pressure
Do not continue with the other checks if the correct gas inlet pressure
can not be achieved.
Check the gas supply working pressures in the system conform to the
readings shown in the table shown in section 6.6 "Checking gas inlet
pressure".
8.7 Checking the flue integrity
NOTICE:
Check flue joints are secure, the terminal and the terminal guard, if
fitted are clear and undamaged.
Combustion testing must be carried out by a competent person.
Testing must not be attempted unless the person carrying out the
combustion check is equipped with a calibrated Flue Gas Analyser
conforming to BS 7967 and is competent in its use.
Flue gas analysis
Ensure that the gas inlet pressure has been checked and is
satisfactory.
Refit the test point plugs after the test has been completed.
Refer to section 6.10 "Checking flue integrity" and check that the
readings conform to those given, confirming flue system and
combustion circuit are ok.
8.8 Flue gas analysis
NOTICE:
Combustion testing
Combustion testing must be carried out by a competent person.
Testing must not be attempted unless the person carrying out the
combustion check is equipped with a calibrated flue gas analyser
conforming to BS 7967 and is competent in its use.
Set the appliance to maximum and minimum output in chimney
sweep mode for the flue gas analysis checks ( chapter 6.4).
Check that the readings conform to those given in the following
tables. In addition to CO and CO/CO
2
ratio checks also check the
maximum and minimum CO
2
percentage reading.
Table 25 CO
2
and O
2
contents
If the CO
2
is out of tolerance then please check:
The gas inlet pressure.
The gas rate.
The fan test pressure.
The flue and air intake, plus any possible blockages in the condensate
disposal.
The condition of burner.
For leaks or obstructions in the exhaust paths.
▶CO
2
is correctly adjusted.
The gas valve and venturi are factory set and should not need to be
adjusted, if found to be out of tolerance and when all other possible
causes have been checked, please contact the Worcester Bosch Group
Helpline 0330 123 3366.
Appliance
Value [P]
GR8300iW 30 0 mbar to -10,0 mbar
GR8300iW 35 0 mbar to -3,5 mbar
GR8300iW 40 0 mbar to -5,0 mbar
GR8300iW 45 0 mbar to -4,8 mbar
GR8300iW 50 0 mbar to -6,0 mbar
FAN PRESSURE TEST
Appliances
0
-6
-5
-4
-3
-2-1
-8
-7
-10
-9
mbar
GR8300iW 30:
- 10.0
GR8300iW 35:
- 3.5
GR8300iW 40:
- 5.0
GR8300iW 45:
- 4.8
GR8300iW 50:
- 6.0
Clean the Heat Ex. Heat Ex. ok
0010024797-001
Maximum rated output Minimum rated output
Gas type CO
2
O
2
CO CO
2
O
2
CO
Natural gas 9.5 %
± 0.4
4.0 % <250ppm 8.6 %
± 0.4
5.5 % <75ppm
Liquid
propane (LPG)
10.8 %
± 0.4
4.6 % <250ppm 10.2 %
± 0.4
5.5 % <75ppm

Table of Contents

Related product manuals