Technical Specifications/Logs
Greenstar 8000 Life – 6720883866 (2019/04)
66
12 Technical Specifications/Logs
12.1 Technical data
12.1.1 Specifications Regular
Greenstar 8000 Life
Table 29 GR8300iW 30/35
GR8300iW 30 GR8300iW 35
Unit Natural gas Propane
1)
1) Propane/butane mixture for fixed containers with capacity up to 15 000 l.
Natural gas Propane
1)
Gas flow maximum rate – 10 minutes from lighting
Natural Gas
2)
2) The Gas Rate provided assumes the accepted NG average calorific value of 34-9 MJ/m
3
net.
m
3
/h 3.2 – 3.6 –
Propane Gas (LPG) kg/h – 2.3 – 2.7
Central Heating (CH)
Maximum rated heat input (net) (Q
max
) kW 30.2 30.2 34.4 34.4
Maximum rated heat output 40/30 °C kW 31.2 31.2 35.2 35.2
Maximum rated heat output 50/30 °C (P
cond, max
) kW 31.0 31.0 35.0 35.0
Maximum rated heat output 80/60 °C (P
max
) kW 29.6 29.6 33.7 33.7
Minimum rated heat input (net) (Q
min
) kW 3.0 3.0 5.1 5.1
Minimum rated heat output 40/30 °C kW 3.3 3.3 5.5 5.5
Minimum rated heat output 50/30 °C (P
cond, min
) kW 3.2 3.2 5.5 5.5
Minimum rated heat output 80/60 °C (P
min
) kW 2.9 2.9 5.0 5.0
Maximum flow temperature °C 70 70 70 70
Maximum flow temperature possible °C 82 82 82 82
Maximum permissible operating pressure (PMS) bar 2.5 2.5 2.5 2.5
Flue
Flue gas temperature 80/60 °C, max/min load °C 67/56 67/56 72/56 72/56
Flue gas temperature 40/30 °C, max/min load °C 49/31 49/31 52/31 52/31
CO
2
level at max. rated heat output (after 10 minutes) % 9.5 10.8 9.5 10.8
CO
2
level at min. rated heat output (after 10 minutes) % 8.6 10.2 8.6 10.2
NO
x
class – 6 6 6 6
NO
x
rating (EN 15502-1) mg/kWh ≤ 40 ≤ 40 ≤ 40 ≤ 40
Condensate
Maximum condensate rate l/h 3.5 3.5 4.1 4.1
pH value, approx. – 4.5 – 5.0 4.5 – 5.0 4.5 – 5.0 4.5 – 5.0
Electrical
Electrical power supply voltage a.c. V 230 230 230 230
Frequency Hz 50 50 50 50
Maximum power consumption (running) W 82 82 53 53
Maximum power consumption (stand-by) W 1 1 1 1
General data
Appliance protection rating
3)
3) Protection rating may change depending on the control unit/s used on this appliance.
IP X4D X4D X4D X4D
Permissible ambient temperature short time/long time °C 0 – 50/40 0 – 50/40 0 – 50/40 0 – 50/40
Nominal capacity of the appliance l 4.2 4.2 4.2 4.2
Total packaged weight kg 54 54 54 54
Total appliance weight (excluding packaging) kg 46 46 46 46
Lift weight (without front and side panels) kg 40 40 40 40