PAGE 24
Aquavar IPC Start-Up Genie
Xylem
Not Set
Suction Input
Setup Low Suction
Protection Through Digital
Input 27?
Disabled
Select Not Set for Suction Input
Select Disabled for Digital input 27
Select Disabled for Digital input 29
Select Manual Reset Alarm for Under
Pressure Function
Select 30 Seconds for Under Pressure Delay
and 20.0% for Under pressure Difference
Setup High Suction
Protection Through Digital
Input 29?
Disabled
Under Pressure Function
Man. Reset Alarm
Under Pressure Delay
20.0%
Under Pressure Diff.
30s