PAGE 23
Aquavar IPC Start-Up Genie
Xylem
No Water/Loss of Prime
Protection Delay
10 secs
NWLP Restart Attempts
10mins
3
NWLP Restart Time
To enable No Water /
Loss of Prime
functionality, No Flow
Power Calibration must
be run on all pumps in the
system. [OK]
0.00hp 0.00A 0.00kW
Calibration completed. open
the valve. Press [OK] then
down arrow to save results or
[cancel] to discontinue.
Hand Local Running
Once the calibration is completed, select OK
and the down arrow to proceed.
Repeat for all drives if you are in
multi-control.
Select 10 Seconds for No Water Loss of
Prime Protection Delay
Select 10 Mins for NWLP Restart Time
Select 3 for NWLP Restsrt Attemps
Proceed with the down arrow acknowledging
that you are enabling your loss of prime
functionality.
Select OK