10 Attachment
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction 295
Mode
l
Terminal
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
4060
R/L1, S/L2, T/L3 25 6 - 35 18 M5
25 mm
2
2.3 - 2.5
(19.8 - 22)
35 mm
2
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 16 4 - 25 18 M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2 25 6 - 35 18 M5
25 mm
2
2.3 - 2.5
(19.8 - 22)
35 mm
2
4.1 - 4.5
(36 - 40)
B1, B2 10 2.5 - 16 10 M4
1.5 - 1.7
(13.5 - 15)
10 6 - 16 - M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
8-4NS from JST Mfg. Co., Ltd.
R8-4S from NICHIFU Co.,Ltd.