5-14
S-curve Acceleration/Deceleration: C2
User constants for S-curve characteristics are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
C2-01
S-curve
characteristic time
at acceleration start
All sections of the S-curve character-
istic time are set in seconds units.
When the S-curve characteristic time
is set, the accel/decel times will
increase by only half of the S-curve
characteristic times at start and end.
0.00 to
2.50
0.00 s No A A 250H
SCrv Acc @ Start
C2-02
S-curve
characteristic time
at acceleration end
0.00 to
2.50
0.00 s No A A 251H
SCrv Acc @ End
C2-03
S-curve
characteristic time
at deceleration start
0.00 to
2.50
0.00 s No A A 252H
SCrv Dec @ Start
C2-04
S-curve
characteristic time
at deceleration end
0.00 to
2.50
0.00 s No A A 253H
SCrv Dec @ End
Run Command
Output
frequency
Time
On
Off
C2-02 C2-03
C2-04
C2-01