User Constant Tables
5-15
Motor Slip Compensation: C3
User constants for slip compensation are shown in the following table.
* The factory setting will change when the control method is changed.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
C3-01
Slip compensation
gain
Used to improve speed accu-
racy when operating with a
load.
Usually setting is not necessary.
Adjust this constant at the fol-
lowing times.
When actual speed is low,
increase the set value.
When actual speed is high,
decrease the set value.
Used as the applicable control
gain when using flux vector
control.
0.0 to
2.5
1.0* Yes A A 260H
Slip Comp Gain
C3-02
Slip compensation
primary delay time
Slip compensation primary
delay time is set in ms units.
Usually setting is not necessary.
Adjust this constant at the fol-
lowing times.
Reduce the setting when slip
compensation responsive is
slow.
When speed is not stabilized,
increase the setting.
0 to
10000
3000
ms
*
No A A 261H
Slip Comp Time
C3-03
Slip compensation
limit
Sets the slip compensation limit
as a percentage of motor rated
slip.
0 to
250
200% No A No 262H
Slip Comp Limit
C3-04
Slip compensation
selection during
regeneration
0: Disabled.
1: Enabled.
When the slip compensation
during regeneration function
has been activated, as regenera-
tion capacity increases momen-
tarily.
0 or 1 0 No A No 263H
Slip Comp Regen
C3-05
Output voltage limit
operation selection
0: Disabled.
1: Enabled. (The motor flux
will be lowered automati-
cally when the output volt-
age become saturated.)
0 or 1 1 No A A 264H
Output V limit