User Constant Tables
5-29
Multi-function Contact Output Functions
Note Set to 0F when contact input is used for the built-in PLC or not used as multi-function contact input.
Setting
Value
Function
Control Methods
Open
Loop
Vector
Flux
Vector
00 During run (on: Run command is on or voltage is being output) Yes Yes
01 Zero-speed Yes Yes
02 Frequency (speed) agree 1 [L4-02 (detection width) is used] Yes Yes
03
Desired frequency (speed) agree 1 [on: Output frequency = ±L4-01, L4-02 (detection width) is
used and during frequency agree]
Yes Yes
04
Frequency (FOUT) detection 1 [on: +L4-01 ≥ Output frequency ≥ -L4-01, L4-02 (detection
width) is used]
Yes Yes
05
Frequency (FOUT) detection 2 [on: Output frequency (speed) ≥ +L4-01 or output frequency ≤ -
L4-01, L4-02 (detection width) is used]
Yes Yes
06 Inverter operation ready (operation ready: Normal status without error after initialization) Yes Yes
07 During main circuit undervoltage (UV) detection Yes Yes
08 During baseblock (on: during baseblock) Yes Yes
09 Frequency reference selection (on: Frequency reference from operator) Yes Yes
0A Run command selection status (on: Run command from operator) Yes Yes
0B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detection when
on)
Yes Yes
0C
Loss of frequency reference [Effective when L4-05 (operation selection when frequency refer-
ence is lost) is set to 1]
Yes Yes
0E Fault (on: Error other than CPF00 and CPF01 has occurred) Yes Yes
0F Not used (Set when the terminal is used for the built-in PLC or not used.) Yes Yes
10 Minor fault (on: Alarm displayed) Yes Yes
11 Fault reset command active Yes Yes
13 Frequency (speed) agree 2 [L4-04 (detection width) is used] Yes Yes
14
Desired frequency (speed) agree 2 [on: Output frequency = L4-03, L4-04 (detection width) is
used, and frequency agree]
Yes Yes
15
Frequency (FOUT) detection 3 [on: Output frequency
≤ L4-03, L4-04 (detection width) is used]
Yes Yes
16 Frequency (FOUT) detection 4 [on: Output frequency ≥ L4-03, L4-04 (detection width) is used] Yes Yes
17
Overtorque/undertorque detection 1 NC (NC contact: Overtorque/undertorque detection when
off)
Yes Yes
18
Overtorque/undertorque detection 2 NO (NO contact: Overtorque/undertorque detection when
on)
Yes Yes
19
Overtorque/undertorque detection 2 NC (NC contact: Overtorque/undertorque detection when
off)
Yes Yes
1A During reverse run (on: During reverse run) Yes Yes
1B During baseblock 2 (off: During baseblock) Yes Yes
1D During regeneration (on: During regeneration) No Yes
1E Restart enabled (on: Restart enabled) Yes Yes
1F Motor overload (OL1) Yes Yes
30 During torque limit (current control) (on: During torque limit) Yes Yes
31 During speed limit (on: During speed limit) No Yes
37
During run 2 (on: Frequency output, off: Base block, DC injection braking, initial excitation,
operation stop)
Yes Yes