5-30
Analog Inputs: H3
User constants for analog inputs are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
H3-01
Signal level selection
(terminal AI1)
0: 0 to 10 V
1: -10V to 10 V
0 or 1 0 No A A 450H
Term AI1 Signal
H3-02
Gain (terminal AI1) Sets the frequency when 10 V
is input, as a percentage of the
maximum output frequency.
0.0 to
1000.0
100.0% Yes A A 451H
Term AI1 Gain
H3-03
Bias (terminal AI1) Sets the frequency when 0 V is
input, as a percentage of the
maximum frequency.
-100.0
to
100.0
0.0% Yes A A 452H
Term AI1 Bias
H3-04
Signal level selection
(terminal AI2)
0: 0 to 10 V
1: -10 V to 10 V
0 or 1 0 No A A 453H
Term AI2 Signal
H3-05
Multi-function analog
input
(terminal AI2)
Select multi-function analog
input function for terminal AI2.
0 to
1FH
1FH No A A 454H
Term AI2 Sel
H3-06
Gain (terminal AI2) Sets the input gain (level) when
terminal AI2 is 10V. Set
according to the 100% value
selected in H3-05.
0.0 to
1000.0
100.0% Yes A A 455H
Term AI2 Gain
H3-07
Bias (terminal AI2) Sets the input gain (level) when
terminal AI2 is 0V. Set accord-
ing to the 100% value selected
in H3-05.
-100.0
to
100.0
0.0% Yes A A 456H
Term AI2 Bias
H3-08
Signal level selection
(terminal AI3)
0: 0 to 10V
1: -10V to 10V
0, 1 0 No A A 457H
Term AI3 Signal
H3-09
Multi-function analog
input
(terminal AI3)
Select multi-function analog
input
function for terminal AI3.
00 to
1FH
0FH No A A 458H
Term AI3 Sel
H3-10
Gain (terminal AI3) Sets the input gain (level) when
terminal AI3 is 10 V. Set
according to the 100% value
selected in H3-09.
0.0 to
1000.0
100.0% Yes A A 459H
Term AI3 Gain
H3-11
Bias (terminal AI3) Sets the input gain (level) when
terminal AI3 is 0 V. Set accord-
ing to the 100% value selected
in H3-09.
-100.0
to
100.0
0.0% Yes A A 45AH
Term AI3 Bias
H3-12
Signal level selection
(terminal AI4)
0: 0 to 10V
1: -10V to 10V
0 or 1 0 No A A 45BH
Term AI4 Signal
H3-13
Multi-function analog
input
(terminal AI4)
Select multi-function analog
input function for terminal AI4.
00 to
1FH
0FH No A A 45CH