User Constant Tables
5-33
Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
H4-01
Monitor selection
(terminal AO1)
Sets the number of the monitor
item to be output (U1-)
from terminal AO1.
0 to 99 2 Yes A A 470H
Term AO1 Signal
H4-02
Gain (terminal AO1) Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00 Yes A A 471H
Term AO1 Gain
H4-03
Bias (terminal AO1) Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-100.0
to
100.0
0.0% Yes A A 472H
Term AO1 Bias
H4-04
Monitor selection
(terminal AO2)
Sets the number of the monitor
item to be output (U1-)
from terminal AO2.
0 to 99 3 Yes A A 473H
Term AO2 Signal
H4-05
Gain (terminal AO2) Sets the multi-function analog
output 2 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00 Yes A A 474H
Term AO2 Gain
H4-06
Bias (terminal AO2) Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-100.0
to
100.0
0.0% Yes A A 475H
Term AO2 Bias
H4-07
Monitor selection
(terminal AO3)
Sets the number of the monitor
item to be output (U1-)
from terminal AO3.
0 or 99 5 Yes A A 476H
Term AO3 Signal
H4-08
Gain (terminal AO3) Sets the multi-function analog
output 3 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00 Yes A A 477H
Term AO3 Gain