54
Table 4.5 “B” Parameters
Access Level
Name
Address
Description Data
Range Unit Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV
2
0 Operator
1 Terminals
2 Modbus Communication
3 Option Card
b1-01
0180h Reference Source
4 Pulse Input
1 1 Q Q Q Q Q
0 Operator
1 Terminals
2 Modbus Communication
b1-02
0181h Run Source
3 Option Card
1 1 Q Q Q Q Q
0 Ramp to Stop
1 Coast to Stop
2 DC Injection to Stop
b1-03
0182h Stopping Method
3 Coast with Timer
1 0 Q Q Q Q Q
0 Reverse Enabled
b1-04
0183h Reverse Operation
1 Reverse Disabled
1 0 A A A A A
0 Run at Frequency Ref
1 Stop
2
Run at Minimum
Frequency
b1-05
0184h Zero-Speed Operation
3 Run at Zero RPM
1 0 A
0 1 Scan (2.5 ms)
b1-06
0185h Digital Input Scan Time
1 2 Scans (5.0 ms)
1 1 A A A A A
0 Cycle External Run
b1-07
0186h Local / Remote Run Selection
1 Accept External Run
1 0 A A A A A
0 Disabled
b1-08
0187h
Run Command at
Programming Mode
1 Enabled
1 0 A A A A A
0 Disabled
b1-10
01DEh
Zero Speed Operation
Selection
1 Enabled
1 1 A
b2-01
0189h DC Injection Start Frequency
0.0 ~ 10.0 Hz 0.1 Hz 0.5 Hz A A A A A
b2-02
018Ah DC Injection Current 0 ~ 100 % 1 % 50 % A A A
b2-03
018Bh DC Injection Time at Start 0.0 ~ 10.0 Sec 0.01 Sec 0.0 Sec A A A A A
b2-04
018Ch DC Injection Time at Stop 0.0 ~ 10.0 Sec 0.01 Sec 0.5 Sec A A A A A
b2-08
0190h
Magnetic Flux Compensation
Level at Start
0 ~ 1000 % 1 % 0 % A
0
Speed Search Frequency
Method - Disable
1
Speed Search Frequency
Method - Enable
2
Speed Search Current
Method - Disable
b3-01
0191h
Automatic Speed Search at
Start
3
Speed Search Current
Method - Enable
1 2 A A A A
b3-02
0192h
Speed Search Current
(Current Detection Method)
0 ~ 200 % 1 % Cntrl Meth
A A A
b3-03
0193h
Speed Search Decel Time
(Current Detection Method)
0.1 ~ 10.0 Sec 0.1 Sec 2.0 Sec A A
b3-05
0195h
Search Delay
(Either Method)
0.0 ~ 20.0 Sec 0.1 Sec kVA Dep.
A A A A A
b3-10
019Ah
Search Detect Compensation
(Speed Detection Method)
1.0 ~ 1.2 0.01 1.1 A A A
b3-13
019Dh
Observer Proportional Gain
N4-08 During Speed Search
0.1 ~ 2.0 0.1 1 A
0 Disabled
b3-14
019Eh
Bi-directional Search
Selection
(Speed Detection Method)
1 Enabled
1 1 A A A A
b3-17
01F0h
Search Restart Current Level
(Speed Detection Method)
0 ~ 200 % 1 % 150 % A A A
b3-18
01F1h
Search Restart Detection Time
(Speed Detection Method)
0.0 ~ 1.0 Sec 0.01 Sec 0.1 Sec A A A