Table 4.5 “B” Parameters
Access Level
Name
Address
Description Data
Range Unit Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV
2
b3-19
01F2h
Number of Search Restarts
(Speed Detection Method)
0 ~ 10 1 0 A A A
0 High Speed Priority
b3-20
01F3h
Search Priority During Under
Current Detection
(Speed Detection Method)
1 Stop Priority
1 0 A
b4-01
01A3h Delay-On Timer 0.0 ~ 3000.0 Sec 0.1 Sec 0.0 Sec A A A A A
b4-02
01A4h Delay-Off Timer 0.0 ~ 3000.0 Sec 0.1 Sec 0.0 Sec A A A A A
0 Disabled
1
Enabled,
D = Feedback
2
Enabled,
D = Feed Forward
3
Frequency Ref + PID
D = Feedback
b5-01
01A5h PID Mode Selection
4
Frequency Ref + PID
D= Feed Forward
1 0 A A A A A
b5-02
01A6h PID Proportional Gain 0.0 ~ 25.0 0.01 1 R A A A A A
b5-03
01A7h PID Integral Time 0.0 ~ 360.0 Sec 0.1 Sec 1.0 Sec R A A A A A
b5-04
01A8h PID Integral Limit 0.0 ~ 100.0 % 0.1 % 100.0 % R A A A A A
b5-05
01A9h PID Derivative Time 0.0 ~ 10.0 Sec 0.01 Sec 0.0 Sec R A A A A A
b5-06
01AAh PID Limit 0.0 ~ 100.0 % 0.1 % 100.0 % R A A A A A
b5-07
01ABh PID Offset -100.0 ~ 100.0 % 0.1 % 0.0 % R A A A A A
b5-08
01ACh PID Delay Time 0.0 ~ 10.0 Sec 0.01 Sec 0.0 Sec R A A A A A
0 Normal Output
b5-09
01ADh PID Output Selection
1 Inverse Output
1 0 A A A A A
b5-10
01AEh PID Output Gain 0.0 ~ 25.0 0.1 1 A A A A A
0 0 limit
b5-11
01AFh PID Output Reverse Selection
1 Reverse
1 0 A A A A A
0 Disabled
1 Alarm
b5-12
01B0h
PID Feedback Loss Detection
Selection
2 Fault
1 0 A A A A A
b5-13
01B1h
PID Feedback Loss Detection
Level
0 ~ 100 % 1 % 0 % A A A A A
b5-14
01B2h
PID Feedback Loss Detection
Time
0.0 ~ 25.5 Sec 0.1 Sec 1.0 Sec A A A A A
b5-15
01B3h PID Sleep Level 0.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A A A A
b5-16
01B4h PID Sleep Time 0.0 ~ 25.5 Sec 0.1 Sec 0.0 Sec A A A A A
b5-17
01B5h PID Accel/Decel Time 0.0 ~ 25.5 Sec 0.1 Sec 0.0 Sec A A A A A
0 Disabled
b5-18
01DCh PID Setpoint b5-19 Selection
1 Enabled
1 0 A A A A A
b5-19
01DDh PID Setpoint 0.0 ~ 100.0 % 0.1 % 0.0 % A A A A A
b6-01
01B6h Dwell Reference at Start 0.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A A A A
b6-02
01B7h Dwell Time at Start 0.0 ~ 10.0 Sec 0.1 Sec 0.0 Sec A A A A A
b6-03
01B8h Dwell Reference at Stop 0.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A A A A
b6-04
01B9h Dwell Time at Stop 0.0 ~ 10.0 Sec 0.1 Sec 0.0 Sec A A A A A
b7-01
01CAh Droop Level 0.0 ~ 100.0 % 0.1 % 0.0 % R A A
b7-02
01CBh Droop Delay Time 0.03 ~ 2.0 Sec 0.01 Sec 0.05 Sec R A A
0 Disabled
b8-01
01CCh Energy Savings Selection
1 Enabled
1 0 A A A A A
b8-02
01CDh Energy Savings Gain 0.0 ~ 10.0 0.1 Cntrl Meth
R A A A
b8-03
01CEh Energy Savings Filter Time 0.0 ~ 10.0 Sec 0.01 Sec kVA Dep.
R A A A
b8-04
01CFh Energy Savings Coefficient 0.0 ~ 655.0 0.01 kVA Dep.
A A
b8-05
01D0h Power Detection Filter Time
0 ~ 2000 ms 1 ms 20 ms A A
b8-06
01D1h
Energy Savings Voltage
Search Limit
0 ~ 100 % 1 % 0 % A A
b9-01
01DAh Zero Servo Gain 0 ~ 100 1 5 A
b9-02
01DBh Zero Servo Completion Widt
h
0 ~ 16383 Counts 1 Count 10 Counts
A