Table 4.6 “C” Parameters
Access Level
Name
Address
Description Data
Range Unit Default
During
Run
V/f
V/f
w/PG
OLV
FV OLV2
C1-01
0200h Accel Time 1 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec R Q Q Q Q Q
C1-02
0201h Decel Time 1 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec R Q Q Q Q Q
C1-03
0202h Accel Time 2 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec R A A A A A
C1-04
0203h Decel Time 2 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec R A A A A A
C1-05
0204h Accel Time 3 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec A A A A A
C1-06
0205h Decel Time 3 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec A A A A A
C1-07
0206h Accel Time 4 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec A A A A A
C1-08
0207h Decel Time 4 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec A A A A A
C1-09
0208h Fast Stop Time 0.0 ~ 6000.0 Sec 0.1 Sec 10.0 Sec A A A A A
0 0.01 Seconds
C1-10
0209h Accel/Decel Units
1 0.1 Seconds
1 1 A A A A A
C1-11
020Ah
Accel/Decel Switchover
Frequency
0.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A A A A
C2-01
020Bh S-Curve at Accel Start 0.0 ~ 2.5 Sec 0.01 Sec 0.20 Sec A A A A A
C2-02
020Ch S-Curve at Accel End 0.0 ~ 2.5 Sec 0.01 Sec 0.20 Sec A A A A A
C2-03
020Dh S-Curve at Decel Start 0.0 ~ 2.5 Sec 0.01 Sec 0.20 Sec A A A A A
C2-04
020Eh S-Curve at Decel End 0.0 ~ 2.5 Sec 0.01 Sec 0.00 Sec A A A A A
C3-01
020Fh Slip Compensation Gain 0.0 ~ 2.5 0.1 Cntrl Meth
R A A A A
C3-02
0210h Slip Compensation Filter Time
0 ~ 10000 ms 1 ms Cntrl Meth
A A
C3-03
0211h Slip Compensation Limit 0 ~ 250 % 1 % 200 % A A
0 Disabled
C3-04
0212h
Slip Compensation During
Regeneration
1 Enabled
1 0 A A
0 Disabled
C3-05
0213h Output Voltage Limit Selection
1 Enabled
1 0 A A A
C4-01
0215h Torque Compensation Gain 0.0 ~ 2.5 0.01 1.00 R A A A
C4-02
0216h
Torque Compensation Filter
Time
0 ~ 10000 ms 1 ms Cntrl Meth
A A A
C4-03
0217h
Forward Direction Torque
Compensation at Start
0.0 ~ 200.0 % 0.1 % 0.0 % A
C4-04
0218h
Reverse Direction Torque
Compensation at Start
-200.0 ~ 0.0 % 0.1 % 0.0 % A
C4-05
0219h
Torque Compensation at Start
Filter Time
0 ~ 200 ms 1 ms 10 ms A
C5-01
021Bh ASR Proportional Gain 1 Cntrl Meth 0.01 Cntrl Meth
R A A A
C5-02
021Ch ASR Integral Time 1 0.000 ~ 10.000 Sec 0.001 Sec Cntrl Meth
R A A A
C5-03
021Dh ASR Proportional Gain 2 Cntrl Meth 0.01 Cntrl Meth
R A A A
C5-04
021Eh ASR Integral Time 2 0.000 ~ 10.000 Sec 0.001 Sec Cntrl Meth
R A A A
C5-05
021Fh ASR Limit 0.0 ~ 20.0 % 0.1 % 0.0 % A
C5-06
0220h ASR Filter Time 0.000 ~ 0.500 Sec 0.001 Sec Cntrl Meth
A A
C5-07
0221h
ASR Gain Switchover
Frequency
0.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A
C5-08
0222h ASR Integral Limit 0 ~ 400 % 1 % 400 % A A
C5-10
0231h ASR Filter Time 2 0.000 ~ 0.500 Sec 0.001 Sec 0.010 Sec
A
1h Fc=2.0kHz
2h Fc=5.0kHz
3h Fc=8.0kHz
4h Fc=10.0kHz
5h Fc=12.5kHz
6h Fc=15.0kHz
C6-02
0224h Carrier Frequency Selection
Fh C6-03 ~ C6-05
1 kVA Dep.
Q Q Q Q Q
C6-03
0225h Carrier Frequency Maximum
0.4 ~ 15.0 kHz
(kVA Dependent)
0.1 kHz kVA Dep.
A A A A
C6-04
0226h Carrier Frequency Minimum
0.4 ~ 15.0 kHz
(kVA Dependent)
0.1 kHz kVA Dep.
A A
C6-05
0227h Carrier Frequency Gain 0 ~ 99 1 0 A A