63
Table 4.10 “H” Parameters
Access Level
Name Address Description Data Range Unit Default
During
Run
V/f
V/f
w/PG
OLV FV OLV2
0h 3-Wire Control
1h Local/Remote Selection
2h Option/Inverter Selection
3h Multi-Step Reference 1
4h Multi-Step Reference 2
5h Multi-Step Reference 3
6h Jog Frequency Reference
7h Multi-Step Accel/Decel 1
8h External Baseblock NO
9h External Baseblock NC
Ah Accel/Decel Ramp Hold
Bh OH2 Alarm Signal
Ch Terminal A2 Enable
Dh V/F w/ PG Disabled
Eh ASR Integral Reset
Fh
Terminal Not Used
(Set for Network Use)
10h MOP Increase
11h MOP Decrease
12h Forward Jog
13h Reverse Jog
14h Fault Reset
15h Fast-Stop N.O.
16h Motor 2 Selection
17h Fast-Stop N.C.
18h Timer Function Input
19h PID Disable
1Ah Multi-Step Accel/Decel 2
1Bh Program Lockout
1Ch Trim Control Increase
1Dh Trim Control Decrease
1Eh
Analog Frequency Reference
Sample Hold
20h EFX- NO, Always, Ramp
21h EFX- NC, Always, Ramp
22h EFX- NO, Run, Ramp
23h EFX- NC, Run, Ramp
24h EFX- NO, Always, Coast
25h EFX- NC, Always, Coast
26h EFX- NO, Run, Coast
27h EFX- NC, Run, Coast
28h EFX- NO, Always, Fast Stop
29h EFX- NC, Always, Fast Stop
2Ah EFX- NO, Run, Fast Stop
2Bh EFX- NC, Run, Fast Stop
2Ch EFX- NO, Always, Alarm
2Dh EFX- NC, Always, Alarm
2Eh EFX- NO, Run, Alarm
2Fh EFX- NC, Run, Alarm
30h PID Integral Reset
31h PID Integral Hold
32h Multi-Step Reference 4
34h PID SFS Cancel
H1-01 0400h
Digital Input Terminal S3
Function Selection
35h Input Level Selection
1 24h - - - - -