Table 4.11 “L” Parameters
Access Level
Name
Address Description Data
Range Unit Default
During
Run
V/f
V/f
w/PG
OLV
FV OLV2
0 Disabled
1 Standard Fan Cooled
2 Standard Blower Cooled
L1-01
0480h
Motor Overload (OL1)
Motor Selection
3 Vector Duty
1 1 Q Q Q Q Q
L1-02
0481h
Motor Overload (OL1)
Time Constant
0.1 ~ 5.0 min 0.1 min 1.0 min A A A A A
0 Ramp to Stop
1 Coast to Stop
2 Fast-Stop (C1-09)
L1-03
0482h
Motor Overheat (OH3)
Alarm Selection
3 Alarm Only
1 3 A A A A A
0 Ramp to Stop
1 Coast to Stop
L1-04
0483h
Motor Overheat (OH4)
Fault Selection
2 Fast-Stop (C1-09)
1 1 A A A A A
L1-05
0484h
Motor Overheat Filter
Time
0.00 ~ 10.00 Sec 0.01 Sec 0.20 Sec A A A A A
0 Disabled
1 Enabled - L2-02 Time
L2-01
0485h
Power Loss Ride Thru
Selection
2 Enabled - CPU Active
1 0 A A A A A
L2-02
0486h
Power Loss Ride Thru
Time
0.0 ~ 25.5 Sec 0.1 Sec 0.1 Sec A A A A A
L2-03
0487h
Minimum Baseblock
Time
0.1 ~ 5.0 Sec 0.1 Sec 0.5 Sec A A A A A
L2-04
0488h
Voltage Recovery Ramp
Time
0.0 ~ 5.0 Sec 0.1 Sec 0.3 Sec A A A A A
L2-05
0489h
Undervoltage Detection
Level
kVA Dep. 1 VDC kVA Dep.
A A A A A
L2-06
048Ah KEB Decel Time 0.0 ~ 200.0 Sec 0.1 Sec 0.0 Sec A A A A A
L2-07
048Bh
Powerloss Ride Thru
Accel Time
0.0 ~ 25.5 Sec 0.1 Sec 0.0 Sec A A A A A
L2-08
048Ch KEB Frequency Gain 0 ~ 300 % 1 % 100 % A A A A A
0 Disabled
1 General Purpose
L3-01
048Fh
Stall Prevention During
Accel Selection
2 Intelligent
1 1 A A A
L3-02
0490h
Stall Prevention During
Accel Current Level
0 ~ 200 % 1 % 150 % A A A
L3-03
0491h
Stall Prevention During
Accel Constant HP Area
Current Lower Limit
0 ~ 100 % 1 % 50 % A A A
0 Disabled
1 General Purpose
2 Intelligent
L3-04
0492h
Stall Prevention During
Decel Selection
3 Enabled - Braking Resistor
1 1 Q Q Q Q Q
0 Disabled
1 Decel Time 1 (C1-02)
L3-05
0493h
Stall Prevention During
Run Selection
2 Decel Time 2 (C1-04)
1 1 A A
L3-06
0494h
Stall Prevention During
Run Current Level
30 ~ 200 % 1 % 160 % A A
0 Disabled
L3-11
04C7h
Overvoltage Inhibit
Selection
1 Enabled
1 0 A A A
L3-12
04C8h
Overvoltage Inhibit
Voltage Level
kVA Dep. 1 V kVA Dep.
A A A
L4-01
0499h Speed Agree Level 0.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A A A A
L4-02
049Ah Speed Agree Width 0.0 ~ 20.0 Hz 0.1 Hz 2.0 Hz A A A A A
L4-03
049Bh Speed Agree Level +/-
-400.0 ~ 400.0 Hz 0.1 Hz 0.0 Hz A A A A A
L4-04
049Ch Speed Agree Width +/-
0.0 ~ 20.0 Hz 0.1 Hz 2.0 Hz A A A A A
0 Stop
L4-05
049Dh
Frequency Reference
Loss Selection
1
Run at L4-06 x Previous
Reference
1 0 A A A A A
L4-06
04C2h
Frequency Reference
Loss Gain
0.0 ~ 100.0 % 0.1 % 80.0 % A A A A A