67 
Table 4.10 “H” Parameters 
Access 
Name
Address 
Digital Operator Display 
Text 
Data
Range  Unit  Default
During
Run
V/f 
V/f 
w/PG
OLV
FV  OLV2
32 ACR (Iq) Output 
33 ACR (Id) Output 
36 PID Input 
37 PID Output 
38 PID Setpoint 
42 Estimated Motor Flux 
43  Id Compensation Value 
44 ASR Output Without Filter 
45  Feed Forward Output 
H4-01
041Dh 
Analog Output Terminal FM
Function Selection 
48 
Stabilizing Speed at Regeneration
(OLV2) 
1  02h    - - - - - 
H4-02
041Eh  Terminal FM Gain  0.0 ~ 1000.0 %  0.1 %  100.0 %
R Q Q Q Q Q 
H4-03
041Fh  Terminal FM Bias  -110.0 ~ 110.0 %  0.1 %  0.0 %  R  A  A  A  A  A 
H4-04
0420h  Terminal AM Selection  See H4-01  1  03h    A  A  A  A  A 
H4-05
0421h  Terminal AM Gain  0.0 ~ 1000.0 %  0.1 %  50.0 %
R Q Q Q Q Q 
H4-06
0422h  Terminal AM Bias  -110.0 ~ 110.0 %  0.1 %  0.0 %  R  A  A  A  A  A 
0 0-10 VDC 
1  -10 +10 VDC 
H4-07
0423h 
Terminal FM Signal Type 
Selection 
(Set Jumper CN15 Also) 
2 4-20 mA 
1  0    A A A A A 
0 0-10 VDC 
1  -10 +10 VDC 
H4-08
0424h 
Terminal AM Signal Type 
Selection 
(Set Jumper CN15 Also) 
2 4-20 mA 
1  0    A A A A A 
H5-01
0425h 
Terminals R+, R-, S+, S-
Modbus Node Address 
0h ~ 20h  1  1Fh    A A A A A 
0 1200 bps 
1 2400 bps 
2 4800 bps 
3 9600 bps 
H5-02
0426h Baud Rate 
4 19200 bps 
1  3    A A A A A 
0 No Parity 
1 Even Parity 
H5-03
0427h Parity Selection 
2 Odd Parity 
1  0    A A A A A 
0  Ramp to Stop 
1  Coast to Stop 
2 Fast-Stop (C1-09) 
H5-04
0428h 
Communication Loss Fault
(CE) Response Selection 
3 Alarm Only 
1  3    A A A A A 
0 Disabled 
H5-05
0429h 
Communication Loss Fault
(CE) Selection 
1 Enabled 
1  1    A A A A A 
H5-06
042Ah  Transmit Wait Time  5 ~ 65 ms  1 ms  5 ms    A  A  A  A  A 
0 Disabled 
H5-07
042Bh RTS Control Selection 
1 Enabled 
1  1    A A A A A 
0 0.1V 
H5-10
0436h 
Unit Selection for Modbus 
Register 0025h (Output 
Voltage Reference Monitor)
1 1V 
1  0    A A A A A 
0 Frequency Reference 
1 PID Feedback 
H6-01
042Ch 
Pulse Input Terminal RP 
Function Selection 
2 PID Setpoint 
1  0    A A A A A 
H6-02
042Dh  Pulse Input Scaling  1000 ~ 32000 Hz  1 Hz  1440 Hz
R A A A A A 
H6-03
042Eh  Pulse Input Gain  0.0 ~ 1000.0 %  0.1 %  100.0 %
R A A A A A 
H6-04
042Fh  Pulse Input Bias  -100.0 ~ 100.0 %  0.1 %  0.0 %  R  A  A  A  A  A 
H6-05
0430h  Pulse Input Filter Time  0.00 ~ 2.00 Sec  0.01 Sec
0.1 Sec
R A A A A A 
1 Frequency Reference 
2 Output Frequency 
20  Soft Starter (SFS) Output 
24 PID Feedback 
31  Not Used (Set for Network Use)
H6-06
0431h 
Pulse Output Terminal MP 
Function Selection 
36 PID Input 
1  02h  R A A A A A 
H6-07
0432h  Pulse Output Scaling  0 ~ 32000 Hz  1 Hz  1440 Hz
R A A A A A