66 
 
Table 4.10 “H” Parameters 
Access 
Name
Address 
Digital Operator Display 
Text 
Data
Range  Unit  Default 
During
Run
V/f 
V/f 
w/PG
OLV
FV  OLV2
0h Frequency Bias 
1h Frequency Gain 
2h 
Auxiliary Reference 1 
(Replaces D1-02) 
3h 
Auxiliary Reference 2 
(Replaces D1-03) 
4h Voltage Bias 
5h Accel/Decel Gain 
6h  DC Injection Braking Current 
7h 
Overtorque/Undertorque 
Detection Level 
8h 
Stall Prevention During Run 
Level 
9h Reference Lower Limit 
Ah Jump Frequency 
Bh PID Feedback 
Ch PID Setpoint 
Dh  Frequency Bias 2 
Eh Motor Temperature 
10h
Forward Torque Limit 
11h
Reverse Torque Limit 
12h
Regenerative Torque Limit 
13h
Torque Reference 
14h
Torque Compensation 
15h
Torque Limit 
H3-05
0414h 
Analog Input Terminal A3 
Function Selection 
1Fh
Not Used 
(Set for Network Use) 
1  02h    - - - - - 
H3-06
0415h  Terminal A3 Gain  0.0 ~ 1000.0 %  0.1 %
100.0 % R A A A A A 
H3-07
0416h  Terminal A3 Bias  -100.0 ~ 100.0 %  0.1 %
0.0 %  R A A A A A 
0 0-10 VDC 
1  -10 +10 VDC 
H3-08
0417h 
Analog Input Terminal 
A2 Signal Type Selection 
(Set Switch S1-2 Also) 
2 4-20 mA 
1  2    A A A A A 
H3-09
0418h  Terminal A2 Selection  0  See H3-05  1  0h    A  A  A  A  A 
H3-10
0419h  Terminal A2 Gain  0.0 ~ 1000.0 %  0.1 %
100.0 % R A A A A A 
H3-11
041Ah  Terminal A2 Bias  -100.0 ~ 100.0 %  0.1 %
0.0 %  R A A A A A 
H3-12
041Bh 
Analog Input Filter Time 
(Applies to A1, A2, and A3)
0.00 ~ 2.00 Sec 
0.01 
Sec 
0.03 Sec   A A A A A 
1 Frequency Reference 
2 Output Frequency 
3 Output Current 
5 Motor Speed 
6 Output Voltage 
7 DC Bus Voltage 
8 Output Power (kW) 
9 Torque Reference 
15  Terminal A1 Level 
16  Terminal A2 Level 
17  Terminal A3 Level 
18 Motor Secondary Current 
19 Motor Excitation Current 
20  Soft Starter (SFS) Output 
21 ASR Input 
22 ASR Output 
24 PID Feedback 
26 Voltage (Vq) Reference 
H4-01
041Dh 
Analog Output Terminal FM
Function Selection 
27 Voltage (Vd) Reference 
1  02h    - - - - -