65
Table 4.10 “H” Parameters
Access Level
Name
Address Description Data
Range Unit Default
During
Run
V/f
V/f
w/PG
OLV
FV OLV2
1Bh
Baseblock 2
1Ch
Motor 2 Selected
1Dh
Regenerating
1Eh
Restart Enabled
1Fh
Overload (OL1)
20h
OH Pre-alarm
30h
In Torque Limit
31h
In Speed Limit
32h
In Speed Limit (Torque
Control Only)
33h
Zero Servo Complete
37h
During Run 2
H2-01
040Bh
Digital Output Terminal
M1-M2 Function Selection
38h
drive Enable
1 0h - - - - -
H2-02
040Ch Terminal M3-M4 Selection
See H2-01 1 1h A A A A A
H2-03
040Dh Terminal M5-M6 Selection
See H2-01 1 2h A A A A A
H2-04
040Eh Terminal P3-C3 Selection See H2-01 1 06h A A A A A
H2-05
040Fh Terminal P4-C4 Selection See H2-01 1 10h A A A A A
0 0-10 VDC
H3-01
0410h
Analog Input Terminal
A1 Signal Type Selection
1 -10 +10 VDC
1 0 A A A A A
H3-02
0411h Terminal A1 Gain 0.0 ~ 1000.0 % 0.1 % 100.0 % R A A A A A
H3-03
0412h Terminal A1 Bias -100.0 ~ 100.0 % 0.1 % 0.0 % R A A A A A
0 0-10 VDC
H3-04
0413h
Analog Input Terminal
A3 Signal Type Selection
1 -10 +10 VDC
1 0 A A A A A