5 Common Drive Specifications
12 YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Item Specification
Momentary Power
Loss Ride-thru
Stops when power loss is longer than 15 ms.
Continues operation if power loss is shorter than 2 s (depending on parameter settings).
Note:
Stop time may be shortened depending on the load and motor speed.
Drive capacity will change the continuous operation time.
Heatsink Overheat
Protection
Thermistor
Braking Resistor
Overheat Protection
Overheat detection for braking resistor (optional ERF-type, 3% ED)
Stall Prevention
Stall prevention is available during acceleration, deceleration, and during run.
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects ground faults during run. The drive will not provide protection when:
There is a low-resistance ground fault for the motor cable or terminal block
Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
DC Link Choke
Built-in to models 5382 to 5472
Table 5.3 Environment
Item
Specification
Area of Use
Indoors
Power Supply
Overvoltage Category III
Permitted Frequency Fluctuation: ±5%
Permitted Voltage Fluctuation: -15% to +10%
Three-phase AC power supply 500 V to 600 V at 50/60 Hz
DC power supply 675 V to 848 V
Ambient Temperature
Setting
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)
When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
Do not let the drive freeze.
You can use IP20/UL Open Type drives at a maximum of 60 °C (140 °F) when you derate the output current.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
Oil mist, corrosive or flammable gas, or dust
Metal powder, oil, water, or other unwanted materials
Radioactive materials or flammable materials, including wood
Harmful gas or fluids
Salt
Direct sunlight
Altitude
1000 m (3281 ft) maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
Vibration
10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
20 Hz to 55 Hz:
5382 to 5472: 0.2 G (2.0 m/s
2
, 6.56 ft/s
2
)
Installation
Orientation
Install the drive vertically for sufficient airflow to cool the drive.