YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
iQpump Micro
Quick Start Procedure
Page 18
of 31
5.24
On IP66/NEMA 4X, UL Type 4X models, insert the digital operator cable from the front cover into port CN1 on the
drive.
Table 1.20 Insert Digital Operator Cable
IP20/NEMA 1, UL Type 1 IP66/NEMA 4X, UL Type 4X
Not applicable.
Drive
CN1 Port
Inside Front Cover
Insert Digital
Operator Cable
5.25
To complete the installation procedure on IP66/NEMA 4X, UL Type 4X enclosures, reattach the front cover of the
drive enclosure. Refer to Table 1.22 for tightening torque specifications.
NOTICE: Damage to Equipment. Take proper precautions when wiring the 24V Power Supply unit so that the front covers will
easily fit back onto the drive. Make sure no cables are pinched between the front covers and the drive when replacing the cover.
Failure to comply may result in damage to circuitry and equipment.
Table 1.21 Attach Enclosure Front Cover
IP20/NEMA 1, UL Type 1 IP66/NEMA 4X, UL Type 4X
Not applicable.
Front Cover
Front Cover Screw (4)
Drive
Table 1.22 IP66/NEMA 4X, UL Type 4X Enclosure Front Cover Installation Bolt Size and Tightening Torque
Voltage Class Drive Model Installation Screw Size
Tightening Torque N
m (lb-in)
Single-Phase 200 V Class BV0001G to BV0012G M5 2.0 to 2.5 (17.7 to 22.1)
Three-Phase 200 V Class
2V0001G to 2V0020G M5 2.0 to 2.5 (17.7 to 22.1)
2V0030G to 2V0069G M6 5.4 to 6.0 (47.8 to 53)
Three-Phase 400 V Class
4V0001G to 4V0011G M5 2.0 to 2.5 (17.7 to 22.1)
4V0018G to 4V0038G M6 5.4 to 6.0 (47.8 to 53)
Install the 24 V Transducer Power Supply (continued)