4 Start-Up Programming & Operation
128 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
When the lightest load direction is up, the drive stops after Light Load Direction Search and then accelerates upwards to
the Rescue Operation speed set in parameter S4-15. The output terminals set for “Light Load Direction” (H2- = 54)
and “Light Load Direction detection status” (H2- = 55) will close.
Figure 68
Figure 75 Light Load Direction Detection (Up)
When the lightest direction is down, then after Light Load Direction Detection is finished the drive immediately
accelerates to the Rescue Operation speed set in S4-15 without stopping. An output terminal set for “Light load
direction” (H2- = 54) will stay open, and an output terminal set for “Light Load Direction detection status”
(H2- = 55) will close.
Figure 69
Figure 76 Light Load Direction Detection (Down)
H1-غغ = 55
(Rescue Operation)
Up
Off (open)
Off (open)
Up
Down
Speed agree torque calculations
Elevator moves in the
direction of the light load
Up/Down command
Up command (internal)
Down command (internal)
On (closed)
On (closed)
Light Load Direction Search status
H2- = 55
Light load direction
H2- = 54
Off (open)
Off (open)
On (closed)
On (closed)
H1-غغ = 55
(Rescue Operation)
Up
Off (open)
Off (open)
Down
Speed agree torque calculations
Elevator moves in the
direction of the light load
Up/Down command
Up command (internal)
Down command (internal)
On (closed)
On (closed)
Light Load Direction Search status
H2- = 55
Light load direction
H2- = 54
Off (open)
Off (open)
On (closed)