7 Option Card Installation
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 159
Option Card
Installation
7
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications
listed in Table 54 for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 54 Crimp Terminal Sizes
6. Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to
the outside. For drive models CIMR-LU20008 through 20033, 40005 through 40018, and 50003
through 50010, cut out the perforated openings on the left side of the drive front cover as shown in Figure 95-A
and leave no sharp edges to damage wiring.
Route the wiring inside the enclosure as shown in Figure 95-B for drive models CIMR-LU20047 through
20415, 40024 through 40605, and 50013 through 50200 that do not require routing through the front
cover.
Figure 86
Figure 95 Wire Routing Examples
Wire Gauge
mm
2
Phoenix Contact Model
L
mm (in)
d1
mm (in)
d2
mm (in)
0.25 (24 AWG)
AI 0.25 - 6YE
AI 0.25 - 6BU
10.5 (13/32) 0.8 (1/32) 2 (5/64)
0.34 (22 AWG) AI 0.34 - 6TQ 10.5 (13/32) 0.8 (1/32) 2 (5/64)
0.5 (20 AWG) AI 0.5 - 6WH 12 (15/32) 1.1 (3/64) 2.5 (3/32)
A – Route wires through the openings
provided on the left side of the
front cover.
<1>
(CIMR-LU20008 through 20033,
40005 through 40018, and
50003 through 50010)
<1> The drive will not meet IP20/NEMA 1, UL Type 1 requirements if wiring is exposed outside the
enclosure.
B – Use the open space provided
inside the drive to route option
wiring.
(CIMR-LU20047 through 20415,
40024 through 40605, and
50013 through 50200)
TOEP_C710616_38H_7_0.book 159 ページ 2015年11月11日 水曜日 午後7時40分