B Parameter Table
174 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
d6: Field Forcing
d1-25
Rescue Operation Speed Sets the speed reference during inspection operation.
Default:
10.00%
<6>
Min: 0.00%
Max: 100.00% <6>
d1-26
Leveling Speed Sets leveling speed reference when d1-18 = 1 or 2.
Default: 8.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
d1-27 Motor 2 Speed Reference
Sets the speed reference for motor 2.
Note:
1. If set to 0.00, the drive will control motor 1 instead.
2. When using motor 2, be sure that the accel/decel times are set in parameters C1-12
and C1-13.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 200.00 Hz
d1-28
Leveling Speed Detection
Level
Used when d1-18 = 0 or 3. If the speed reference selected is lower than d1-28, then
the drive uses the leveling speed as the speed reference.
Default: 0.0%
Min: 0.0%
Max: 100.0%
d1-29
Inspection Speed Detection
Level
Used when d1-18 = 0 or 3. If the speed reference selected is higher than d1-28 but
lower or equal to d1-29, then the drive uses inspection speed as the speed reference.
Default: 0.0%
Min: 0.0%
Max: 100.0%
<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 215.
No. Name Description Setting
d6-03 Field Forcing Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
d6-06 Field Forcing Limit
Sets the upper limit of the excitation current command during magnetic field forcing.
A setting of 100% is equal to motor no-load current. Disabled only during DC
Injection Braking.
Default: 400%
Min: 100%
Max: 400%