B Parameter Table
192 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
L5: Automatic Fault Reset
L6: Torque Detection
No. Name Description Setting
L5-01
Number of Auto Reset
Attempts
Sets the number of times the drive may attempt to reset after the following faults
occur: GF, LF, oC, ov, rr, oH1, oL1, oL2, oL3, oL4, UL3, UL4.
Default: 0
Min: 0
Max: 10
L5-02
Fault Output Operation
during Auto Reset
0: Fault output not active.
1: Fault output active during reset attempt.
Default: 0
Min: 0
Max: 1
L5-06
Undervoltage Fault Reset
Selection
0: Same as L5-01 condition
1: Always automatically reset UV1
Default: 0
Min: 0
Max: 1
No. Name Description Setting
L6-01
Torque Detection Selection
1
0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
Default: 0
Min: 0
Max: 8
L6-02 Torque Detection Level 1 Sets the overtorque and undertorque detection level.
Default: 150%
Min: 0%
Max: 300%
L6-03 Torque Detection Time 1
Sets the time an overtorque or undertorque condition must exist to trigger torque
detection 1.
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
L6-04
Torque Detection Selection
2
0: Disabled
1: oL4 detection only active during speed agree, operation continues after detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4 fault
4: oL4 detection always active during run, output shuts down on an oL4 fault
5: UL4 detection only active during speed agree, operation continues after detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4 fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
Default: 0
Min: 0
Max: 8
L6-05 Torque Detection Level 2 Sets the overtorque and undertorque detection level.
Default: 150%
Min: 0%
Max: 300%
L6-06 Torque Detection Time 2
Sets the time an overtorque or undertorque condition must exist to trigger torque
detection 2.
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
TOEP_C710616_38H_7_0.book 192 ージ 015年11月11日 水曜日 午後7時40