2 Mechanical Installation
18 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
■ Installation Orientation and Spacing
WARNING! Fire Hazard. Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply
could result in overheating and fire. When drives are placed inside the same enclosure panel, install proper cooling to ensure air
entering the enclosure does not exceed 40
°
C (104
°
F).
Installation Orientation
Install the drive upright as illustrated in Figure 2 to maintain proper cooling. Refer to Mechanical Installation on
page 17 for details on installing the drive.
Figure 3
Figure 2 Correct Installation Orientation
Installation Spacing
Figure 3 shows the installation distance required to maintain sufficient space for airflow and wiring.
Figure 4
Figure 3 Correct Installation Spacing
A – 50 mm (1.97 in.) minimum C – 120 mm (4.72 in.) minimum
B – 30 mm (1.18 in.) minimum D – Airflow direction
A
A
BB
Side Clearance Top/Bottom Clearance
C
C
D
D
TOEP_C710616_38H_7_0.book 18 ページ 2015年11月11日 水曜日 午後7時40分