C Standards Compliance
226 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C (167°F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40°C (104°F).
20145
<2>
R/L1, S/L2, T/L3 4/0 2/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4/0 3/0 to 4/0
–, +1 1 to 4/0
+3 1/0 to 4/0
44 to 2
9 to 11
(79.7 to 97.4)
20180
<2>
R/L1, S/L2, T/L3 1/0 × 2P 1/0 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 1/0 × 2P 1/0 to 2/0
–, +1 1 to 4/0
+3 1/0 to 4/0
4 4 to 1/0
9 to 11
(79.7 to 97.4)
20215
<2>
R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 2 to 300 M10
18 to 23
(159 to 204)
3 3 to 300 M12
32 to 40
(283 to 354)
20283
<2>
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 3/0 to 300 M10
18 to 23
(159 to 204)
2 2 to 300 M12
32 to 40
(283 to 354)
20346
<2>
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600
–, +1 250 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
20415
<2>
R/L1, S/L2, T/L3 350 × 2P 250 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 300 to 600
–, +1 300 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
<1> When an EMC filter is installed, additional measures must be taken in order to comply with IEC/EN 61800-5-1. Refer to EMC Filter
Installation on page 220.
<2> Drive models CIMR-LU20085 to 20415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-LU
Terminal
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
TOEP_C710616_38H_7_0.book 226 ージ 015年11月11日 水曜日 午後7時40

Table of Contents

Other manuals for YASKAWA L1000A