B Parameter Table
176 YASK AWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
F: Option Settings
F parameters are used to program the drive for Encoder and PG feedback from the motor and to function with option
cards.
F1: PG Speed Control Card
E5-11
(333H)
Encoder Offset
Sets the offset between the rotor magnetic axis and the encoder zero position. Set
during Encoder Offset Tuning.
Default: 0.0 deg
Min: -180 deg
Max: 180 deg
E5-24
(353H)
Motor Induction Voltage Constant 2
Sets the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min)
[mechanical angle].
When setting this parameter, E5-09 should be set to 0.0.
Default:
0.0 mV/(r/min)
Min:
0.0 mV/(r/min)
Max:
6500.0 mV/(r/min)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is determined by the drive model (o2-04).
<3> The display resolution depends on the rated output power of the drive. Models 2A0018 to 2A0041 and 4A0009 to 4A0023 display values in 0.01
A units, while models 2A0059 to 2A0432 and 4A0030 to 4A0260 display values in 0.1 A units.
<4> Maximum setting is 48 when PG-E3 option is connected.
No.(Addr.) Name Description Setting
F1-01
(380H)
Encoder 1 Resolution
Sets the encoder resolution (number of pulses per revolution)
Default: <1>
Min: 1 ppr
Max: 60000 ppr <2>
F1-02
(381H)
Operation Selection at PG
Open Circuit (PGo)
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
F1-03
(382H)
Operation Selection at
Overspeed (oS)
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
F1-04
(383H)
Operation Selection at
Deviation
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 3
Min: 0
Max: 3
F1-05
(384H)
Encoder 1 Rotation Direction
Selection
0: A phase leads B in up direction
1: B phase leads A in up direction
Default:
<1>
Min: 0
Max: 1
F1-06
(385H)
PG 1 Pulse Monitor Output
Division Ratio
Sets the division ratio for the pulse monitor used of the PG option card installed
to connector CN5-C. By setting “xyz”, the division ratio becomes = [(1 + x) /
yz]. If only using the A pulse for one track input, then the input ratio will be 1:1,
regardless of what F1-06 is set to.
Default: 1
Min: 1
Max: 132
F1-08
(387H)
Overspeed Detection Level
Sets the overspeed detection level as a percentage of the maximum output
frequency.
Default: 115%
Min: 0%
Max: 120%
F1-09
(388H)
Overspeed Detection Delay
Time
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
Default: 0.0 s
Min: 0.0 s
Max: 2.0 s
No.(Addr.) Name Description Setting
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV
common
_
CLV
CLV/PM
V/f OLV