11 Inspection, Maintenance, and Troubleshooting
11.3.2 Troubleshooting of Warnings
11-38
A.91A:
Converter
Electric
Operation
Overload
The sequence of phase
U, V, and W motor lines
is incorrect.
Check the wiring of the motors main
circuit cable.
Correct the motor wiring.
The motor main circuit
cable is either incor-
rectly wired or has a
contact fault.
Make sure the wiring is correct. Correct the wiring.
A mistake occurred
when selecting the
power regeneration con-
verter capacity.
Check the power regeneration con-
verter capacity and the total output
capacity of the SERVOPACK.
Change the power regeneration con-
verter capacity.
Converter current detec-
tion circuit failure
Turn the power supply OFF and then
ON again. If the warning still occurs,
the power regeneration converter may
be faulty. Replace the power regenera-
tion converter.
The AC power supply
voltage is low.
Measure the power supply voltage.
Set AC power supply voltage within
the specified range.
A.91B:
Converter Power
Supply
Regenerative
Overload
A mistake occurred
when selecting the
power regeneration con-
verter capacity.
Check the power regeneration con-
verter capacity and the total output
capacity of the SERVOPACK.
Change the power regeneration con-
verter capacity.
The AC power supply
voltage is low.
Measure the power supply voltage.
Set AC power supply voltage within
the specified range.
Power regeneration
converter failure
Turn the power supply OFF and then
ON again. If the warning still occurs,
the power regeneration converter may
be faulty. Replace the power regenera-
tion converter.
A.921:
Dynamic Brake
Overload
(Warning before
the alarm A.731
occurs)
The servomotor rotates
because of external
force.
Check the operation status.
Take measures to ensure the servomo-
tor will not rotate because of external
force.
The rotating energy at a
DB stop exceeds the DB
resistance capacity.
Check the power consumed by DB
resistance monitor in SigmaWin for Σ-
V-S D (MT) to see how many time s t h e
DB has been used.
Reconsider the following:
•Reduce the servomotor reference
speed.
•Reduce the moment of inertia ratio.
•Reduce the number of times of the
DB stop operation.
SERVOPACK failure
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A.923:
Built-in Fan in
SERVOPACK
Stopped
The fan inside the SER-
VOPACK stopped.
Check for foreign matter or debris
inside the SERVOPACK.
Remove foreign matter. If the warning
still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.
A.92B:
Built-in Fan in
Converter
Stopped
The fan inside the
power regeneration con-
verter stopped.
Check for foreign matter or debris
inside the power regeneration con-
verter.
Remove the foreign matter. If the
warning still occurs, the power regen-
eration converter may be faulty.
Replace the power regeneration con-
verter.
(cont’d)
Warning
Number:
Warning Name
(Warning
Description)
Cause Investigative Actions Corrective Actions