Power supply
cable
Figure 4.1.7  Electric Cable Wiring for Integral Flowmeter
(4)  DC Power Connection
When using DC power as the power supply for the 
converter, give attention to the following points.
1)  Connecting Power Supply
IMPORTANT
Do not connect power supply with reversed polarities.
L/+ terminal: connect +
N/– terminal: connect –
IMPORTANT
Do not connect power supply with 100 to 240 V
AC or 100 to 120 V DC in the case of a 24 V
power supply version (power supply code 2).
It will give a damage to the converter.
2)  Required Power Supply Voltages
IMPORTANT
Whenusinga24Vpowersupply,thespecicationfor
the supply voltage is 24 V (–15% to +20%), but the input 
voltage of the converter drops due to cable resistance 
therefore it must be used within the following ranges.
Usable range E (V)
Cable cross section area: 1.25 mm
2
Cable cross section area: 2 mm
2
length m(ft)
0
20.4 22 24 26 28.8
200 (  660)
796 (2610)
796 (2610)
796 (2610)
Figure 4.1.8   Supply Voltage and Cable Length for Integral 
Flowmeter
3)  Setting Power Supply Frequency
IMPORTANT
Set the local commercial power frequency in order to 
eliminate the effect of induction noise from the power 
supply.
Referto“ParameterDescription”intheuser’smanual
of the AXF Integral Flowmeter [Software Edition] (IM 
01E20C02-01E).
Parameter No.: J30 and J31
(5) Grounding
CAUTION
Be sure to connect the protective grounding of the 
AXFintegralowmeterwithacableof2mm
2
 or larger 
cross section in order to avoid electrical shock to the 
operators and maintenance engineers and to prevent 
theinuenceofexternalnoise.
Connect the grounding wire to the 
 mark.
The grounding should satisfy Class D requirements 
(groundingresistance,100Ωorless).
In case of TIIS Flameproof type, the grounding should 
satisfy Class C requirements (grounding resistance, 
10Ωorless)orclassArequirements(grounding
resistance,10Ωorless).
For explosion proof type except TIIS, follow the domestic 
electrical requirements as regulated in each country.
IMPORTANT
When optional code A (lightning protector) is selected, 
the ground should satisfy Class C requirements 
(groundingresistance,10Ωorless).
•  The protective grounding terminals 
 are located on 
the inside and outside of the terminal area.
Either terminal may be used.
• 
Use 600 V vinyl insulation wires as the grounding wires.