Item
Name
R/W
(*3)
Data range
Units
Position of
decimal point
Default value (*):
Indicated item
Description
Display unit (BRAIN) Display unit/BRAIN
C40 Base Flow Unit
(FLOW UNIT)
W Ml(Megaliter)
m
3
kl(Kiloliter)
l(Liter)
cm
3
m
t
kg
g
kcf
cf
mcf
Mgal (US)
kgal (US)
gal (US)
mgal (US)
kbbl (US Oil)
bbl (US Oil)
mbbl (US Oil)
ubbl (US Oil)
kbbl (US Beer)
bbl (US Beer)
mbbl (US Beer)
ubbl (US Beer)
ft
klb (US)
lb (US)
m (*) Selectsowunitsfortheowratespan.
Linked with B21.
C41 Base Time Unit
(TIME UNIT)
W /d
/h
/min
/s
/s (*) Selectstimeunitsfortheowratespan.
Linked with B22.
C42 Flow Span
(FLOW SPAN)
W 0.0001 to 32000 C40/C41
(B21/B22)
0 to 4 1 m/s (*) Setsowratespan(withunitsfromC40
and C41). Linked with B23.
C43 Flow Decimal Pnt
(FLOW DECIMAL)
W Auto
0
1
2
3
Auto (*) Selects decimal point position for the
display unit's instantaneous flow rate.
Linked with B24.
C44 Velocity Check
(VELOCITY CHK)
R 0.000 to 99.999 m/s 3 Display of the span setting using flow
velocity (m/s).
C45 Density Unit
(DENSITY UNIT)
W kg/m
3
lb/gal
lb/cf
kg/m
3
Sets units for density when mass flow
rate is selected.
C46 Mass Flow Density
(MASS DENSITY)
W 0 to 32000 C45 0 to 4 0 Sets density when mass flow rate is
selected (with units from C45).
C47 User Span Select
(USER SPN SEL)
W No
Yes
No Selects whether or not special units are
usedforowrateunits.
C48 Flow User Unit
(FL USER UNIT)
W 8 alphanumeric
characters
ALL SPACE Setsthespecialowrateunits.
C49 Flow User Span
(FL USER SPAN)
W 0.0001 to 32000 C48 0 to 4 100 Sets span when using special flow rate
units.
C60 —
(SELF CHECK)
R Good
Error
See Chapter 7.
D00 Total Set
(TOTAL SET)
D10 Total Unit
(TOTAL UNIT)
W n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
Pulse/s (*) Selects the flow rate unit per one pulse
as used for totalization display. Linked
with B30.
D11 Total Scale
(TOTAL SCALE)
W 0 to 32000 D10
(B30)
0 to 4 0 (*) Sets the flow rate per one pulse for the
totalization display.Linked with B31.
D12 Total Decimal Pnt
(TL DECIMAL)
W 0
1
2
3
4
5
6
7
0 Selects position of decimal point for
totalization display
D13 Total Low Cut
(TOTAL LOWCUT)
W 0 to 100 % 0 3 % Sets the range in vicinity of 0% within
which the totalization display will be
halted.
*3: R/W: R = Read only, W = Read and Write