<8. Parameter Summary>
71
IM 01E20A01-01EN
Item
Name
R/W
(*3)
Data range
Units
Position of
decimal point
Default value (*):
Indicated item
Description
Display unit (BRAIN) Display unit/BRAIN
F12
(*1)
SI1 Function
(SI1 FUNCTION)
W No Function
0% Singal Lock
Ext Auto Zero
Ext Ttl Preset
Ext Rev Ttl Set
Ext 2 Ranges
Ext 3 Ranges
Ext 4 Ranges
No Function Selects function for the SI1 terminal
F13
(*1)
SI2 Function
(SI2 FUNCTION)
W No Function
0% Singal Lock
Ext Auto Zero
Ext Ttl Preset
Ext Rev Ttl Set
Ext 2 Ranges
Ext 3 Ranges
Ext 4 Ranges
No Function Selects function for the SI2 terminal
F14
(*1)
SO1/2 Active Mode
(SO ACT MODE)
W Closed(On) Act
Open(Off) Act
Closed(On) Act Selects whether SO1/SO2 output will be
setto“OnActive”or“OffActive.”
F15
(*1)
SI1/2 Active Mode
(SI ACT MODE)
W Short Active
Open Active
Short Active Selects whether SI1/SI2 input will be set
to“ShortActive”or“OpenActive.”
F20
(*2)
DO Function
(DO FUNCTION)
W No Function
Pulse Output
Alarm Output
Warning Output
Total Switch (O)
H/L Alarm (O)
HH/LL Alarm (O)
Fwd/Rev Rngs (O)
Auto 2 Rngs (O)
Auto 3 Rngs (O)
Auto 4 Rngs (O)
Ext 2 Answer (O)
Pulse Output Selects function for the DO terminal
F21
(*2)
DIO Function
(DIO FUNCTION)
W No Function
Alarm Output
Warning Output
Total Switch (O)
H/L Alarm (O)
HH/LL Alarm (O)
Fwd/Rev Rngs (O)
Auto 2 Rngs (O)
Auto 3 Rngs (O)
Auto 4 Rngs (O)
Ext 2 Answer (O)
0% Singal Lock (I)
Ext Auto Zero (I)
Ext Ttl Set (I)
Ext R Ttl Set (I)
Ext 2 Ttl Set (I)
No Function Selects function for the DIO terminal
F22
(*2)
DO Active Mode
(DO ACT MODE)
W Closed(On) Act
Open(Off) Act
Closed(On) Act Selects whether DO terminal will be set
to“OnActive”or“OffActive”.
F23
(*2)
DIO Active Mode
(DIO ACT MODE)
W Closed/Short Act
Open/Open Act
Closed/Short Act Selects whether DIO terminal will be set
to“Closed/ShortActive”or“Open/Open
Active”.
F30 Forward Span2
(FWD SPAN2)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for forward No. 2
range
F31 Forward Span3
(FWD SPAN3)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for forward No. 3
range
F32 Forward Span4
(FWD SPAN4)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for forward No. 4
range
F33 Reverse Span1
(REV SPAN1)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for reverse No. 1
range
F34 Reverse Span2
(REV SPAN2)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for reverse No. 2
range
F35
(*1)
Reverse Span3
(REV SPAN3)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for reverse No. 3
range
F36
(*1)
Reverse Span4
(REV SPAN4)
W 0.0001 to 32000 C40/C41 0 to 4 1 Sets flow rate span for reverse No. 4
range
F40 Auto Range Hys
(AUTO RNG HYS)
W 0 to 15 % 0 10 % Sets hysteresis width for automatic
range switching
F41 Bi Direction Hys
(BI DIREC HYS)
W 0 to 8 % 0 2 % Sets hysteresis width for forward/
reverse switching
F60
(SELF CHECK)
R Good
Error
See Chapter 7.
*1: Applicable for AXFA11 Remote Converter.
*2: Applicable for AXF Integral Flowmeter and AXFA14 Remote Converter.
*3: R/W: R = Read only, W = Read and Write
Parameter Summary
8