Item
Name
R/W
(*3)
Data range
Units
Position of
decimal point
Default value (*):
Indicated item
Description
Display unit (BRAIN) Display unit/BRAIN
G00 Alarm
(ALARM)
G10 Low Alarm
(LOW ALARM)
W -110 to 110 % 0 -110 % Setslevelsettingvalueforlowowrate
limit (L)
G11 High Alarm
(HIGH ALARM)
W -110 to 110 % 0 110 % Setslevelsettingvalueforhighowrate
limit (H)
G12 Low Low Alarm
(LO LO ALARM)
W -110 to 110 % 0 -110 % Setslevelsettingvalueforlow-lowow
rate limit (LL)
G13 High High Alarm
(HI HI ALARM)
W -110 to 110 % 0 110 % Sets level setting value for high- high
owratelimit(HH)
G14 H/L Alarm Hys
(H/L ALM HYS)
W 0 to 10 % 0 5 % Sets hysteresis width for high-low flow
rate limit alarm
G20
(*1)
Alm Out Act Mode
(ALM OUT ACT)
W Closed(On) Act
Open(Off) Act
Open(Off)
Act
Selects whether alarm output will be set
to“OnActive”or“OffActive.”
G21 4-20mA Alarm Out
(4-20 ALM OUT)
W 2.4mA or Less
4.0mA
Hold
21.6mA or More
21.6mA or More Selects the current output during alarm
occurrence.
G22 4-20mA Burn Out
(4-20 BURNOUT)
R High Low Displays the current output during a
CPU failure.
G30 Alm-Setting
(ALM-SETTING)
W No
Yes
Yes Selects whether a setting alarm is to be
speciedasanalarm.
G31 Alm-Sig Over
(ALM-SIG OVER)
W No
Yes
Yes Selectswhetherasignaloverowalarm
istobespeciedasanalarm.
G32 Alm-Emp Pipe
(ALM-EMP PIPE)
W No
Yes
Yes Selects whether an empty pipe alarm is
tobespeciedasanalarm.
G33 Alm-HH/LL
(ALM-HH/LL)
W No
Yes
No Selectswhetheraowratehigh-highor
low-low alarm is to be specified as an
alarm.
G34 Alm-Adhesion
(ALM-ADHESION)
W No
Yes
No Selects whether an electrode adhesion
alarmistobespeciedasanalarm.
G40 Operation Time
(OPERATE TIME)
R 0D 00:00 to
99999D 23:59
Operation time
G41 Alm Record1
(ALM RECORD1)
R 10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
15:Coil Open
16:EEPROMDt
18:Power Off
19:Inst Pwr Fail
28:WDT
30:SigOverow
31:Empty Pipe
33:Adhesion Alm
Displays the content of the most recent
alarm.
G42 Alm Record Time1
(ALM TIME 1)
R 0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the most recent alarm.
G43 Alm Record2
(ALM RECORD2)
R
Same as G41
(Alm Record 1)
Displays the content of the second most
recent alarm.
G44 Alm Record Time2
(ALM TIME 2)
R 0D 00:00 to
99999D 23:59
Displays the operation time at
occurrence of the second most recent
alarm.
G45 Alm Record3
(ALM RECORD3)
R
Same as G41
(Alm Record 1)
Displays the content of the third most
recent alarm.
G46 Alm Record Time3
(ALM TIME 3)
R 0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the third most recent
alarm.
G47 Alm Record4
(ALM RECORD4)
R
Same as G41
(Alm Record 1)
Displays the content of the fourth most
recent alarm.
G48 Alm Record Time4
(ALM TIME 4)
R 0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the fourth most recent
alarm.
G60
(SELF CHECK)
R Good
Error
See Chapter 7.
H00 Display Set
(DISP SET)
H10 Display Select1
(DISP SELECT1)
W Flow Rate(%)
Flow Rate
Flow Rate(mA)
Forward Total
Reverse Total
Dif Total
Flow Rate Selects content of the first line for
Display Mode. Linked with B40.
*1: Applicable for AXFA11 Remote Converter.
*3: R/W: R = Read only, W = Read and Write
<8. Parameter Summary>
72
IM 01E20A01-01EN