1. System Installation Requirements
1-33
TI 33Q01J10-01E
1.7 Corrosive-gas Environment Compatibility
The CS 3000 system employs ER bus node units and FIO input/output modules which
meet the ANSI/ISA G3 environment requirements and are compatible with the corrosive
gas-susceptible environment.
G3 Environment-compatible Products
Table G3 Environment-compatible Products (1/2)
No. Product Model Description
1
Field control
unit
AFF50
-1
Compact Field control unit (for FIO)
2 Node unit
ANR10
-3
ER bus node unit (19-inch Rack Mount type)
3
Analog I/O
modules
AAI141-3
Analog input module (4 to 20 mA, 16-channel, non-isolated)
AAV141-3
Analog input module (1 to 5 V, 16-channel, non-isolated)
AAV142-3
Analog input module (–10 to +10 V, 16-channel, non-isolated)
AAI841-3
Analog I/O module
(4 to 20 mA input, 4 to 20 mA output, 8-channel/8-channel, non-isolated)
AAB841-3
Analog I/O module
(1 to 5 V input, 4 to 20 mA output, 8-channel/8-channel, non-isolated)
AAV542-3
Analog output module (–10 to +10 V, 16-channel, non-isolated)
AAP149-1
Pulse input module for compatible PM1
(16-channel, pulse count, 0 to 6 kHz, non-isolated)
AAP849-1
Pulse input/Analog output module for compatible PAC
(Pulse count input, 4 to 20mA output, 8-channel/8-channel, non-isolated)
AAI143-3
Analog Input Module (4 to 20 mA, 16-Channel, Isolated)
AAI543-3
Analog Output Module (4 to 20 mA, 16-Channel, Isolated)
AAV141-3
Analog input module (–10 to +10 V, 16-channel, isolated)
AAV544-3
Analog output module (–10 to +10 V, 16-channel, isolated)
AAT141-3
Thermocouple/mV input module (16-channel, isolated)
AAR181-3
Resistance temperature detector input module (12-channel, isolated)
AAI135-3
Analog input module (4 to 20 mA, 8-channel, isolated channels)
AAI835-3
Analog I/O module (4 to 20 mA, 4-channel/4-channel, isolated channels)
AAT145-3
Thermocouple/mV input module (16-channel, isolated channels)
AAR145-3
Resistance temperature detector/potentiometer input module
(16-channel, isolated channels)
AAP135-3
Pulse input module (8-channel, 0 to 10 kHz, isolated channels)
Sep. 30, 2008-00