2. Transportation, Storage and Installation
2-6
TI 33Q01J10-01E
2.2 Unpacking
In unpacking the received cargoes and equipment, inspect them according to inspection
list below. It is recommended to unpack by Yokogawa engineers or in their presence.
Table Inspection List
Inspection Items Result Measures Required
Exterior
• Environment of unpacking location
(temperature, humidity, dust)
Suitable Unsuitable If unsuitable, select proper location according to
specified environmental requirements.
• Rapid temperature fluctuation
(should be within ±10 °C/h)
No Yes If yes, do not unpack and wait until the
fluctuation remains within ±10 °C/h.
• Damage to equipment exterior
No Yes
If damaged badly, inform Yokogawa.
• Condensation or its trace on
equipment exterior. (*1)
No Yes If yes, inform Yokogawa.
Interior
• Loose parts inside equipment.
No Yes
If yes, remove them and check the surrounding.
• Damage to equipment interior.
No Yes
If damaged badly, inform Yokogawa.
• Condensation or its trace on
equipment interior. (*1)
No Yes If yes, inform Yokogawa.
*1: Condensation symptoms are as follows:
• Dew patterns on PCBs.
• Printed circuit copper trace is floating off the board.
• Label characters on PCBs are smudged.
• Connectors on PCBs are smudged.
• Dew patterns or traces of droplets are found on cabinet panels.
Condensation may cause a fatal system failure in the CS 3000 system. Be sure to unpack
the equipment indoor under the specified environmental conditions. Strictly observe the
allowable temperature fluctuation range of ±10 °C/h. Do not bring the equipment into a heated
room straight from the outside in winter. Our warranty does not cover any damage caused by
condensation. Proper treatment may be able to minimize the damage caused by condensation,
however. Contact Yokogawa in case of condensation.
Be careful not to let the products fall when you handle them.
When they are hit hard, the interior of them can be damaged, although there is no damage in the
exterior.
If you accidentally drop an product, stop using it immediately and report it to YOKOGAWA or
YOKOGAWA’s service department.
May 18, 2007-00