<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF digitalYEWFLO>
A1-10
IM 01F06F00-01EN
Relative
Index
Index Parameter Name Factory Default
Write
Mode
Explanation
82 2082 NOISE_RATIO Indicates the noise balance ratio. When the value of
NOISE_BALANCE_MODE is 1 (Auto), this value cannot
be modied. When it is 2 (Manual), the desired value can
be set as a xed ratio.
83 2083 SIGNAL_LEVEL 1 O/S Sets the signal level. Setting range: 0.1 to 20.0
84 2084 FLOW_VELOCITY Indicates the current ow velocity in m/s (1061); updated
periodically.
85 2085 SPAN_VELOCITY Indicates the span ow velocity in m/s (1061); updated
periodically. (This parameter is set to the value calculated
based on the density under the normal operating
conditions and normal operating temperature specied by
the customer.)
86 2086 VORTEX _
FREQUENCY
Indicates the current vortex generation frequency in Hz
(1077); updated periodically.
87 2087 SPAN_FREQ Indicates the vortex generation frequency at the span
ow in Hz (1077); updated periodically. (This parameter
is set to the value calculated based on the density under
the normal operating conditions and normal operating
temperature specied by the customer.)
88 2088 FLUID_DENSITY Indicates the uid density calculated based on the
temperature data, in the unit determined by DENSITY_
UNIT; updated periodically.
89 2089 SENSOR _ERROR
_RECORD
0 O/S,
AUTO
Record of the following errors regarding the sensor. This
record will be automatically cleared when no error has
occurred for a month.
Recorded errors: Flow over output, Span set error, Pre-
amp fault, EEPROM fault, Sensor fault, Transient noise,
High vibration, Clogging, Fluctuating, Temp over output,
Over temp, Temp sensor fault, Temp convert fault.
Setting range: 0 only. Setting 0 clears the record.
90 2090 MODEL digitalYEWFLO O/S,
AUTO
Model of the owmeter converter
91 2091 ALARM_SUM 0 O/S,
AUTO
Indicates the entire block’s alarm statuses; Disable can
only be set.
153 2153 VOLUME_FLOW Indicates the volumetric ow rate.
154 2154 VOLUME _FLOW_
UNIT
Indicates the unit of VOLUME_FLOW. It links the unit of
XD_SCALE of AI3.
Note 1: The value changes in line with a change to the SIZE_SELECT value or to the unit setting in XD_SCALE of the corresponding AI
block.
Note 2: An intended value which meets both of the following conditions can only be written: CAL_POINT_LO < the intended value, and
SENSOR_RANGE.EU100 > intended value.
Note 3: An intended value which meets both of the following conditions can only be written: CAL_POINT_HI < the intended value, and
SENSOR_RANGE.EU100 > intended value.
Note 4: The ow rate unit can only be written.
Note 5: These parameters are set in accordance with the specications written in the registered sizing data if it is supplied.
In case of UNCALIBRATION order, they are set to the defaults when shipped.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA digitalYEWFLO Series and is the answer not in the manual?

YOKOGAWA digitalYEWFLO Series Specifications

General IconGeneral
BrandYOKOGAWA
ModeldigitalYEWFLO Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals