<7. Errors and Countermeasures>
52
IM01C25A01-01E
Table 7.2 Alarm Message Summary (For EJX910A and EJX930A, HART protocol type)
Integral
indicator
Cause
4-20mA Output
operation during error
Countermeasure
AL. 01
CAP.ERR
Sensorproblem. Outputsthesignal(HighorLow)set
withburnoutdirectionswitch.
[statusoutput:undened]
Replacecapsuleiftheerrorrecurs
afterthetransmitterisrestarted.
Capsuletemperaturesensorproblem. Replace capsule.
CapsuleEEPROMproblem.
AL. 02
AMP.ERR
Ampliertemperaturesensorproblem. Replaceamplier.
AmplierEEPROMproblem.
Amplierproblem.
A/DConverterproblem.
AL. 03
ET.ERR
Externaltemperaturesensor
disconnection.
Checkexternaltemperaturesensor.
NodeviceIDisfound. Continuestooperateandoutput. Replaceamplier.
AL. 10
PRESS
Differential pressure is outside
measurement range limit of capsule.
WhenPVisPres
OutputAOupperlimitorAOLower
limit.
Checkinputorreplacecapsulewhen
necessary.
AL. 11
ST. PRSS
Staticpressureexceedslimit. WhenPVisSP
OutputAOupperlimitorAOLower
limit.
AL. 12
CAP.TMP
Capsuletemperatureisoutsiderange
(–50to130°C).
Continuestooperateandoutput. Useheatinsulationormakelagging
tokeeptemperaturewithinrange.
AL. 13
AMP.TMP
Ampliertemperatureisoutsiderange
(–50to95°C).
AL. 14
EXT. TMP
Externaltemperatureisoutsiderange. WhenPVisET
OutputAOupperlimitorAOLower
limit.
AL. 15
EXT. TMP
Externaltemperaturesensorresistance
isoutspecication.
AL. 16 PLS Pulseoutputisoutspecication. Continuestooperateandoutput. Checksettingsandchangethem.
AL. 30
PRS.RNG
Differentialpressureexceedsspecied
range.
WhenPVisPres.
Output AO upper limit or lower limit.
Checkinputandrangesetting,and
changethemasneeded.
AL. 31
SP. RNG
Staticpressureexceedsspecied
range.
WhenPVisSP
Output AO upper limit or lower limit.
AL. 32
F. RNG
Flowexceedsspeciedrange. WhenPVisFlow
Output AO upper limit or lower limit.
AL. 33
ET. RNG
Externaltemperatureexceedsspecied
range.
WhenPVisET
Output AO upper limit or lower limit.
AL. 35 P.HI Inputpressureexceedsspecied
threshold.
Continuestooperateandoutput. Checkinput.
AL. 36 P.LO
AL. 37 SP.HI Inputstaticpressureexceedsspecied
threshold.
AL. 38 SP.LO
AL. 41 F.HI Inputowexceedsspeciedthreshold.
AL. 42 F.LO
AL. 43 ET.HI Inputexternaltemperatureexceeds
speciedthreshold.
AL. 44 ET.LO
AL. 50 P. LRV Speciedvalueisoutsideofsetting
range.
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL. 51 P. URV
AL. 52 P. SPN
AL. 53 P. ADJ Continuestooperateandoutput. Adjustsettingsandchangethemas
needed.
AL. 54
SP. RNG
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL. 55
SP. ADJ
Continuestooperateandoutput. Adjustsettingsandchangethemas
needed.
AL. 56
ET. RNG
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL. 57
ET. ADJ
Continuestooperateandoutput. Adjustsettingsandchangethemas
needed.
AL. 58
FL. ADJ
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL. 59
PLS.ADJ
Speciedvalueisoutsideofsetting
pulse output.
Normalcalculation.
UnderTemperatureFixMode.PVisET Temp.OutputFixat4mA.
LeavefromTemperatureFixMode.