1-39
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
Index
Explanation
Linearizer Approximation
Corrects input values using characteristics specified with segments to derive output values.
Output value
Measured value
Input value
Number of setpoints: 2 to 12
( )
Linearizer Bias
Corrects input values using bias values specified with segments to derive output values.
Input value
Number of setpoints: 2 to 12
Linearizer bias
After correction
Output value
Measured value
( )
Correction Factor
Corrects input values using the instrument correction factor and sensor correction factor
specified with segments to derive output values.
Input value
Number of setpoints: 2 to 12
Instrument correction factor + Sensor correction factor
After correction
Output value
Measured value
( )
Uncorrected value
1.2ConfiguringAIChannels(Analog(includingDI)input)channelsandAI(mA)channels