EasyManuals Logo

YOKOGAWA RAMC User Manual

YOKOGAWA RAMC
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
<6. ELECTRONIC TRANSMITTER (-E)>
6-21
IM 01R01B02-00E-E 12th edition October 01, 2014 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
Float-Blocking-Indication (F7x)
Function F71: On-/Off- switching of the oat-blocking-indication
Description Selection Key Indication
Change to setting mode Enter
Display mode
F1-
Setting mode 6 x
Enter
F 7-
F71
Selection
or
FBI OFF/ON
FBI ON/OFF
Enter
Enter
F71
F72
F71
Back to display mode
F 7-
Display mode
Function F72: Selection of the lower limit value of the supervision range
Description Selection Key Indication
Change to setting mode Enter
Display mode
F1-
Setting mode 6 x
Enter
F 7-
F71
F72
Selection
or
or
5% of Qmax
15% of Qmax
30% of Qmax
Enter
Enter
Enter
Enter
F72 -5
F72
F72 -15
F72
F72 -30
F72
Back to display mode
F 7-
Display mode
Function F73: Selection of the supervision time
Description Selection Key Indication
Change to setting mode Enter
Display mode
F1-
Setting mode 6 x
Enter
2 x
F 7-
F71
F73
Selection
or
5 Minutes
15 Minutes
Enter
Enter
Enter
F73 -5
F73
F73 -15
F73
Back to display mode
F 7-
Display mode
Function F74:Start Autozero function and storage
Description Selection Key Indication
Change to setting mode Enter
Display mode
F1-
Setting mode 6 x
Enter
3 x
F 7-
F71
F74
Selection
Inquire autozero value (80s)
Display autozero value (10s)
Autozero Enter
Enter
F74 -1
0.000
0.xxx
Back to display mode
F 7-
Display mode

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA RAMC and is the answer not in the manual?

YOKOGAWA RAMC Specifications

General IconGeneral
BrandYOKOGAWA
ModelRAMC
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals